- Infrared (infrared) fire detector in aluminum housing with CPD EN54-10 and SIL2 certificates. It incorporates a microprocessor for flame signal analysis, with multiple alarm levels that can be adjusted and manually checked. Detect hydrocarbon fuel fires and gas fires with an advanced flame analysis system. It has alarm, fault and auxiliary relay outputs NA.
- Requires S40/40-001 and 24Vdc 150mA power support. For explosive areas, it also requires an F-81212N cable gland. Recommended for interiors only. Optional of models with 4-20mA analog output and without auxiliary relay. Check room availability.
• Coverage: 15 meters with an angle of 90º H - 90º V.
• Shell material: Aluminum
• Weight: 1.7Kg
• Certificate: 0832-CPD-0978; SIRA Ex II 2 GD EEx IIB + H2 T5 Amb temp: -55 C to +75º C; EEx IIB + H2 T4 Amb. Temp .: -55 C to +85º C.