RP1R-SUPRA ,Notifer central fire alarm catalog normal type

Manufacture: Notifire
Product code: RP1R-SUPRA

Central fire alarm catalog Notifer normal type RP1R-SUPRA
⭐Supplying 1 loop hochiki addressable fire alarm control panel, quotation of hochiki fire alarm system, fire alarm, fire alarm equipment, firenet fire alarm center, warranty Genuine 12 months , 100% new , Commitment to nationwide delivery

Zalo

Consulting hotline: 0944934114
Product information

- Output circuits to indicate siren output with three phases, Gas burnout indication, dual extinction circuit controlled by programmed time and circuit to close gate and signal system status brand. EN-12094 approved.

- Check availability

• Supply voltage: 90 to 264 Vac 50 / 60Hz

• Zones: 3 zones for configurable coincidence detection and activation

• Maximum battery charge current: 300mA (7A/h battery)

• Maximum current at siren output: 2 x 250mA

• Maximum auxiliary current: 2 x 250mA (fixed and resettable)

• Maximum extinguishing current: 1Amp

• Display: 2 digits x 7 segments LED

• Indication LED: 42 for quick event identification

• Relays: 10 NO relays to control e Status indicator and 2 OC outputs

• Standby power consumption: 125mA

• Maximum battery charge current: 300mA (7A/h battery)

• Cockpit protection level: IP30

• Internal history: last 450 events

• Equipment Environment Class: Class A

• Operating temperature: -5ºC to +40ºC

• Relative humidity: 95% non-condensing

• Configurable delay (30-300 seconds) and test time (1-10 minutes)

• Configurable Digital Inputs: System Reset, Evacuate, Silent or On/Off

• Dimensions in mm: 381 (width) x 353 (height) x 123 (bottom)

• Compliant with European standards: EN54-2/4 and EN12094/1: 2003

• CPD Certificate: 1134-CPD-045

- Compact hub with 32-bit microprocessor. Two conventional detection zones for the detector, plus a third configuration for the detector or manual trigger. 2 siren outputs. 2 auxiliary power outputs (fixed and reset). 2 extinguishing circuit. Automatic short circuit protection on all outputs. It incorporates a log of the last 450 events for viewing later in the program to show plant status and restore history. Separate input for extinguishing stop button and standby button. Option to cancel delay keypad, with push button alarm or with 2 alarm zones. Flow detection input, low pressure, door opening monitoring, mechanical extinction cancellation. Two extinguishing circuits. Displayed with countdown indicator in seconds. 42 LEDs for quick event identification. Relay for each system state. Contact input for programmed remote actions such as: System Reset, Evacuate, Silence or On/Off Delay. Removable strip on all connections. The program displays the status the PC.

You can refer to products genuine fire alarm equipment...HERE

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about RP1R-SUPRA ,Notifer central fire alarm catalog normal type

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.16482 sec| 4329.828 kb