The 3-zone carbon monoxide detection center can be expanded to 5 zones. The compact cabin includes 1 control module, 3 P-100 modules, power supply and 24Vdc emergency voltage input.
• Main supply voltage: 230Vac + -10%
• Supply control module: 24Vdc
• Maximum power per P-100 zone module: 8.4W at 24Vdc
• Final rate range: 300 ppm
• Operating temperature: -10ºC to 50ºC
• Zone connection: Two twisted and shielded 1.5 mm2 . wires
• Maximum linear distance per zone: 500m
• Maximum number of detectors per zone: 16 detectors
• 2 outputs for extraction: 250V / 10A . dry contact
• 1 Alarm output: 120Vac/1A dry contact. 30Vdc / 1 A
• 1 Error output: 120Vac/1A dry contact. 30Vdc / 1 A
• Weight: 5.6Kg
• Dimensions in mm: 357 (height) x 382 (width) x 94 (depth)
• Certificate: LOM08MOGA3658