Description of Notifier M710-CZR Domain Controller Addressing Module
The M710-CZR non-addressable area monitoring module allows an area of unaddressable probes to communicate with a Notifier analog addressing system. As a result, existing loops can be integrated an address system that announces single-area monitoring modules of dual-address wireless smoke detectors. The M710-CZR uses one of the 159 available module addresses on a loop. The non-addressable zone can be powered line analog communication or an external power supply. Where the non-addressable zone is powered an external power source, the communication line is completely isolated the non-addressable zone and the mains. This M710-CZR Unaddressed Area Monitoring Module is suitable for M200E-SMB, M200E-DIN or M200E-PMB. These can then be installed in the 19 19 Rack Assembly using mounting adapters.
Notifier M710-CZR . Domain Controller Addressing Module Specifications
Size:
- Height: 93 mm
- Width: 83 mm
- Depth: 23mm
• Weight: 110 g
• Maximum wire gauge for 2.5mm2 . terminals Power and consumption parameters Notifier M710-CZR . zone control addressable module
• Standby up to 500uA @ 24V (communication every 5 seconds with LED blinking activated, with external power supply for zero addressable area)
• Maximum standby current 6.7mA @ 24V (communication every 5 seconds with LED blinking trigger, loop provides no zone address, R.EOL only)
• Current LED @ 24Vdc Red: 2.2μA Green: 6.6A Yellow: 8.8μA
• Up to 60mA . area-limited non-addressable
• External power supply voltage 12 - 28.5V
• Maximum series resistance 50Ω
• End-of-line resistor value: 3.9k Environmental Specifications Notifier M710-CZR . Domain Controller Addressing Module
• Temperature range: -20°C to +60°C
• Humidity: 5% to 95% relative humidity (non-condensing)