ISO-X addressable notifier isolation module Loop SLC
Address monitoring module Addressable module for conventional detectors, hochiki addressable fire alarms, dcp-som-a, lamp control module, how to connect r2ml module, hochiki r2m module, 12 month warranty, full delivery No quantity, Contact 0917.911.114
Descriptions ISO-X addressable notifier isolation module Loop SLC
- ISO-X Isolation Module - Loop (SLC)
- The Notifer ISO-X fault isolation module is to be used with the AFP-2800 and AFP-2802 to protect the system against short-circuiting wires on the SLC loops.
Features ISO-X - Loop (SLC) Addressable Notifier Isolator Module
• Powered by direct SLC loop, no external power required.
• Mounts in a standard 10.16 cm square Junction box is 5,398cm deep.
• The built-in LED flashes to indicate normal conditions. Stable illumination when short circuit condition is detected.
• High noise immunity (EMF/RFI).
• Wide viewing angle of LEDs.
• SEMS screws with clamp plates for easy wiring.
• Automatic open loop SLC short detection, preventing short causing failure of the entire loop.
• Auto reset on short calibration
Applications ISO-X addressable notifier isolation module Loop SLC
- Fault isolation modules must be spaced between groups of sensors in a loop to protect the rest of the loop. Used to isolate short-circuits in one part of a loop so that other parts can continue to function properly. ISO-X supports up to 25 devices in between isolators.
Work
- Automatically opens circuit when line voltage drops below four volts. Error Isolator modules should be spaced between groups of addressable devices (up to 25) in a loop to protect the rest of the loop.
- If a short occurs between two isolators, then both isolators immediately switch to an open circuit state and isolate groups of sensors between them. The rest of the units on the loop continue to function fully.
- The ISO-X fault isolation module automatically restores the missing part of the incoming communication loop to normal condition when the short circuit condition is cleared.
Specifications ISO-X addressable notifier isolation module Loop SLC
- Loop (SLC)
- Operating voltage: 15 - 32 VDC (peak).
- Current range: 5 mA for LED latch in alarm. Standby current: 400 A max, plus supervision current.
- Pulse current: 30 mA for 15 mS (FCM-1).
- Temperature range: 0°C to 49°C.
- Relative humidity: 10% to 93% (No condensation).