The FAAST LT-200 suction smoke detection system is equivalent to the FL0111E-HS model with 2 highly sensitive IR LED detectors.
- Operating voltage: 18.5 ... 31.5 Vdc
- Static current @ 24 Vdc approx. 270 mA
- Operating temperature: -10°C ... 55°C
- Relative humidity: 10 ... 93% (non-condensing)
- Protection index: IP 65
- Shell: plastic (ABS)
- Black
- Weight: approx. 6.5 kg (including sensor)
- Dimensions: A: 356 mm H: 403 mm F: 135 mm
- Certificate 0832-CPR-F1051
- High sensitivity IR LED detection technology
- Approved for grades A, B and C
- Up to 18 holes in class C, 6 in class B and 3 in class A per channel
- Ultrasonic Flow Measurement The unique design of the pendulum reading line allows to verify the functionality of the pipeline network
- Monitor and transmit flow failure through relay
- Record 2240 events
- USB interface
You can refer to products genuine fire alarm equipment...HERE