FAAST-LT-200 automatic smoke detection system. Kit includes 1 highly sensitive LED transducer, ultrasonic flow sensor and protected electronics. The FAAST-LT-200 includes alarm and pre-alarm levels that can be set between 9 sensitivity levels. A pendulum graphic bar with 9 airflow levels verifies that the airflow is in accordance with the requirements of EN54-20. Information can be easily and quickly read in the user interface or via a USB connection using the TubeIQ LT program.
- Operating voltage: 18.5 ... 31.5 Vdc
- Static current @ 24 Vdc approx. 170 mA
- Operating temperature: -10°C ... 55°C
- Relative humidity: 10 ... 93% (non-condensing)
- Protection index: IP 65 - Shell: plastic (ABS)
- Black
- Weight: approx. 6.5 kg (including sensor)
- Dimensions: A: 356 mm H: 403 mm F: 135 mm
- Certificate: 0832-CPR-F1050
- High sensitivity IR LED detection technology
- Approved for grades A, B and C
- Up to 18 holes in class C, 6 in class B and 3 in class A per channel
- Ultrasonic Flow Measurement The unique design of the pendulum reading line allows to verify the functionality of the pipeline network
- Monitor and transmit flow failure through relay
- Record 2240 events
- USB interface
You can refer to products genuine fire alarm equipment...HERE
You will receive a quote from us as soon as possible..
Have 0 comment, evaluate about FL0111E-HS,Independent suction system 1 channel 1 detector
TVAdministratorsAdministrators