FAAST LT 200 Single Loop Fire Alarm Sensor System

Manufacture: Notifire
Product code: NFXI-ASD11-HS-EB, NFXI-ASD12-HS-EB, NFXI-ASD22-HS-

FAAST™ LT-200 NFXI-ASD11-HS-EB, NFXI-ASD12-HS-EB, NFXI-ASD22-HS-EB , Single Loop Fire Alarm Sensor System FAAST LT 200
⭐Modern fire alarm equipment, the ability to deal with false alarms

Zalo

Consulting hotline: 0944934114
Product information

FThe AAST LT-200 provides a viable solution for applications where standard detection methods are prone to failure or false alarms. Designed with installers and end-users in mind, this instrument serves a wide range of EN54-20 Class C applications where maintenance differentials, other methods of smoke detection, are not suitable, due to harsh environments. or cosmetically problematic areas. The LT-200 detector offers the ultimate in connectivity to the overall system. The unit is quick to set up, easy to set up, and includes TubeIQ LT installation and commissioning software.

Hệ thống Cảm Biến Báo Cháy Kết Vòng Lặp đơn FAAST LT 200

Mechanical Specifications Single Loop Fire Alarm Sensor System FAAST LT 200

• Height 403 mm (including inlet and outlet) • Width 356 mm

• Depth 135 mm

• Top and bottom pre-drilled 3-hole M20 cable access

• 0.5mm2 to 2mm2 . tape measure

• Single pipe length up to 90 m

• Total branching pipe length up to 160 m (per channel)

• Up to 18 air intake holes (per channel)

• Outer diameter 25 mm or 27 mm

• Inner tube diameter 15-21 mm

• Sensitivity (obscure) range 0.07 - 0.66% obs/m (Alarm level 1-5)

• Relay 2 (1 Alarm, 1 Fault) x per channel

• Audio output 1 per channel • Event Log 2244 events

• Terminal Block Interface: power supply, relay, audio output, external input; Loop connection, USB port; Buttons (Test, Reset, Off)

• Power supply and relay connections up to 2 mm2

• Standard USB cable for USB Type-C connection

• Shipping weight 6.5kg (dual channel) including packing

• Flow monitoring and reporting High & Low according to EN54-20

• Filter replaceable filter

• Programmable 10-speed fan control

Electrical Specifications Single Loop Fire Alarm Sensor System FAAST LT 200

• Smoke sensor High sensitivity LED detection

• External supply voltage 18.5 - 31.5 VDC

• 2 seconds remote reset time

• Reset power 0.5 seconds

• Operating current (audio not included) 1-channel device 170mA @ 24 VDC 2-channel device 270mA @ 24 VDC

• Max. Alarm Current (not including sound) 1-channel device 360mA @ 24 VDC 2-channel device 570mA @ 24 VDC

• Relay contact rating 2.0 A @ 30 VDC, 0.5 A @ 30 VAC

• Loop supply voltage 15-29 VDC (Loop current ≤ 900mA) Standby loop current @ 24V 900 A max. (poll every 5 seconds) Environmental parameters FAAST LT 200 . Single Loop Fire Alarm Sensor System

• Operating temperature -10°C to 55°C

• Humidity 10 to 93% (non-condensing)

• IP IP Rating List and Approval of the FAAST LT 200 . Single Loop Fire Alarm Sensor System

• LPCB

• EN54-20 (holes per channel) Type C - 18 holes

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..