Description Duct Notifier Duct Smoke Detector InnovairFlex D2
- The Notifer InnovairFlex D2 is a photoelectric smoke detector with a revolving housing suitable for many applications: both square and rectangular footprint mounts to round or rectangular ductwork.
- This new chimney smoke detector senses airspeeds 0.5 to 20.32 meters per minute with proven accuracy. Improvements built this model improve false alarm immunity (with sensor head plug-in); Extended operating temperature (-20°C to 70°C) and humidity (0 to 95 percent non-condensing) ranges; while simplifying installation and maintenance. Advanced features can detect smoke even in the harshest ducting applications.
- New design provides additional wiring space with an extra 20 mm conduit. The number and label for the designated terminal match the previous model renewal. The new sampling tube can be clicked place with one smooth movement the front or back of the detector.
- The Notifer InnovairFlex D2 chimney has a signal to indicate trouble and maintenance conditions. In addition, a tamper feature is incorporated to indicate a troublesome condition for previous sensor installation or removal. An innovative cover design, low integration, low-tech magnetic sensor head isolation for simple maintenance.
Features Duct Notifier Duct Smoke Detector InnovairFlex D2
• Photovoltaic, Low Integration Technology
• Rated air velocity 0.5 m/s to 20.32 m/s
• Flexible mounting options: square or rectangular
• Wide range for operating temperature (-20°C to 70°C) and humidity (0% to 95% non-condensing)
• Patented sampling tube the front or back of the detector with no tools required
• Covers rogue signals • Increased wiring space with newly added 20 mm . type conduit
• Backwards compatible with existing Innovation Models
• Plugaceble's sensor head
• Compatible with conventional Notifer FIP range Specifications Duct Notifier Duct Smoke Detector InnovairFlex D2
Size:
- (Rectangle) 37 cm Length; Width 12.7 cm, depth 6.36 cm
- (Square) Length 19.7 cm; Width 22.9 cm; Depth 6.35 cm
- Operating temperature range: -20 degrees Celsius to 70 degrees Celsius -
Storage temperature range: -30 degrees Celsius to 70 degrees Celsius Operating Humidity: 0% to 95% relative humidity (no air conditioning)
- Air duct velocity: 0.5 to 20.32 m/s
Duct Notifier Duct Notifier Duct Smoke Detector Electrical Capacity InnovairFlex D2
- Supply voltage: 8.5-35 VDC
- Input capacitance: 0.1uF . max
- Reset voltage: 2.5 VDC min
- Reset time: (when power off): up to 0.3 seconds
- Power-on time: up to 35 seconds
- Alarm response time: 15 seconds
Request Duct Notifier Duct Smoke Detector InnovairFlex D2
- Peak standby current: 120uA
- Maximum standby current: 60uA (average)
- Maximum alarm current: 130mA
Video Duct Notifier Duct Smoke Detector InnovairFlex D2