Maximum 30 meters of detection range with a 100 degree cone of vision.
Permits operation at Hazardous areas.
User selectable output options among Relays, 4-20㎃ stepped output, and RS-485.
Highlights
• UV/IR Dual-sensors
• Wide field of view
• Enhanced False Alarm Immunity against sunlight and artificial false alarm sources
• Explosion-Proof and Dust Ignition proof
• Suitable for hazardous areas such as Oil, Gas stations and Petrochemical plants
• Field selectable sensitivity and delay time
Specification
• Type : Ultraviolet and Infrared, Outdoor, Explosion-proof
• Nominal sensing range : 30m
• Sensing angle : 100°, Cone type
• Operating temp. : -40 ~ +75°C
• Keeping temp. : -50 ~ +90°C
• Humidity : 0~95%
• performance :
- FM3260
- GB 12791(CCC), EN 50130-4(CE)
• Explosion proof :
- T5/T6, IP67, Ex d IIC (KGS)
- Ex tD A21 IP67 T100°C (KGS)
- II 2 G Ex d IIC T5/T6 Gb(ATEX)
- Ex dIIC T5/T6 Gb(NEPSI)
• water tight : IP67(KGS)
• Output signal
- Relay
Fire : 1A ( 250VAC, 30VDC ), A-B connect point
Error : 1A ( 250VAC, 30VDC ), A-B connect point
- 4~20mA
- RS485
• Function
- Diagnostic sensor fault enable - Self test
- Remote self diagnostic ON/OFF control ( BIT )
[ Structure ]
• Material : Aluminum 6061
• Surface : Anodizing Process
• Color : White silver
• Weight : About 0.53kg
• External : 64 × 64 × 75mm, Hexahedral, Connector 1/2 NPT
[ Electrical ]
• Power Cunsumption : 2.0W minimum / 3.6W maximum
• Voltage : DC 24V, ( 17~32V, pulsating current enable)
• Current
- Idel(Sensing) :55mA
- Fire(Activating, Emergency)(Sensing) : 90mA
- Self test : 170mA
Certificates and Documents
• ATEX Approval
• CCC Approval
• NEPSI Approval
• CE Approval
• Russia Fire Approval
• Russia Ex Approval
• KFI Approval
• KGS Approval
• KGS Dust Ex Approval
• FM3260 Approval
• RFD-2FTN catalog
• RFD-2FTN Layout Drawing
Have 0 comment, evaluate about UVIR Flame Detector RFD-2FTN
TVAdministratorsAdministrators