SLC Fault Isolator Module FX-ISO
SLC Fault Isolator Module FX-ISO ⭐
✅ Kidde intelligent modules are engineered to deliver high-performance features, superb reliability ⭐
✅ and unbeatable quality. control of ancillary equipment, to enhanced signaling functionality, these products add flexibility and powerful options to Kidde intelligent systems
- Designed expressly for small buildings, Kidde modules are addressable devices that are uniquely identified on the system by means of familiar rotary switches. Once registered, they share data and status information that determines how the system behaves and how connected devices interact with one another.
- Unique to Kidde modules is ground fault detection so precise that it actually pinpoints the specific module where the wiring problem has occurred. This saves hours of troubleshooting and wire tracing. And only Kidde provides this important feature!
- The Kidde family of intelligent modules also offers contractors and installers simple setup and installation, while delivering options that take full advantage of intelligent fire alarm processing. With a microprocessor in each device, intelligence is distributed throughout the system so that command decisions are made instantly at the individual module, rather than bottlenecking at the control panel.
- This not only speeds event processing, it also makes a more robust and reliable system – so robust, in fact, that when upgrading a conventional panel to a Kidde intelligent system, you can usually use existing wiring – no twisted or shielded cable required!
Standard Features
• Class A-B Two-Wire Module
- Acts as an interface between conventional two-wire smoke detectors and the Kidde control panel.
• Analog Class A Single Input Module
- Used to connect a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit to the Kidde control panel.
• Analog Dual Input Module
- Connects two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits to the Kidde control panel.
• Analog Dual Input Waterflow, Supervisory Module
- Used to connect normally open waterflow alarm and supervisory initiating device circuits to the Kidde control panel. For Class B circuit operation.
• Analog SLC Fault Isolator Module
- Protects a Class A SLC total collapse due to wire-to-wire short circuits.
• Analog NAC Module
- Connects a supervised output circuit to a signal riser.
• Analog Contact Relay Module
- Provides one Form C dry relay contact and can be configured to provide polarity reversal of its output.
• Analog Single Input Mini Module
- Connects a normally open, alarm, supervisory, or monitor type dry contact initiating device circuit (IDC) to the Kidde control panel. For Class B circuit operation.
Installation
Mount in a North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box or a standard 4 in. square box 1-1/2 in. (38 mm) deep
SLC Fault Isolator Module FX-ISO
- The FX-ISO protects a Class A SLC total collapse due to wire-to-wire short circuits. The module monitors line voltages and opens the SLC when a short is detected. A short is isolated between the two modules located electrically closest to the short.
- The device address is set using the two rotary switches located on the front of the module. One device address is required.
Communication line voltage | Maximum 20 V peak-to-peak |
Current | |
Standby Activated |
175 μA 200 μA |
Ground fault impedance | 10 k ohm |
Maximum circuit resistance between isolators | 6 ohm |
Operating environment | |
Temperature Humidity |
32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) |
Storage temperature range | –4 to 140°F (–20 to 60°C) |
Compatible electrical boxes | North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep |
Wire size | 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred) |
Module address |
01 to 64 (64 point control panel) 01 to 127 (1000 point control panel) |
Ordering Information
Model | Description | Ship Weight |
FX-IDC1A | Analog Class A Single Input Module | 0.50 lbs. (0.23 kg.) |
FX-IDC1B | Analog Single Input Mini Module | 0.34 lbs. (0.15 kg.) |
FX-2WIRE | Analog Class A-B Two-Wire Module | 0.50 lbs. (0.23 kg.) |
FX-IDC2B | Analog Dual Input Module | 0.50 lbs. (0.23 kg.) |
FX-2IDCWS | Analog Dual Input Waterflow-Supervisory Module | |
FX-NAC | Analog NAC Module | |
FX-RLY | Analog Contact Relay Module | |
FX-ISO | Analog SLC Fault Isolator Module |
Have 0 comment, evaluate about SLC Fault Isolator Module FX-ISO
TVAdministratorsAdministrators