- The device address is set using the two rotary switches located on the front of the module. One device address is required.
- The module is configured to operate as an alarm latching device type the factory. When the NO contact of an initiating device is closed, an alarm signal is sent to the control panel and the alarm condition is latched at the module.
- Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual.
Communication line voltage | Maximum 20 V peak-to-peak |
Current | |
Standby Activated |
350 μA 500 μA |
Ground fault impedance | 10 k ohm |
Operating environment | |
Temperature Humidity |
32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) |
Storage temperature range | –4 to 140°F (–20 to 60°C) |
Wire size | 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred) |
Device address (two addresses required) |
01 to 64 (64 point control panel) 01 to 127 (1000 point control panel) |
Initiating device circuit (IDC) | |
EOL resistor value Max. circuit resistance Max. circuit capacitance |
47 kΩ, (P/N: EOL-47) 50 Ω (25 Ω per wire) 0.1 μF |
Ordering Information
Model | Description | Ship Weight |
FX-IDC1A | Analog Class A Single Input Module | 0.50 lbs. (0.23 kg.) |
FX-IDC1B | Analog Single Input Mini Module | 0.34 lbs. (0.15 kg.) |
FX-2WIRE | Analog Class A-B Two-Wire Module | 0.50 lbs. (0.23 kg.) |
FX-IDC2B | Analog Dual Input Module | 0.50 lbs. (0.23 kg.) |
FX-2IDCWS | Analog Dual Input Waterflow-Supervisory Module | |
FX-NAC | Analog NAC Module | |
FX-RLY | Analog Contact Relay Module | |
FX-ISO | Analog SLC Fault Isolator Module |