Riser Monitor Modules GSA-RM1

Manufacture: kidde
Product code: GSA-RM1

GSA-RM1 Riser Monitor Modules  ⭐
✅ is intelligent analog addressable devices that form part of Kidde’s Signature line of products  ⭐
✅The actual operation of the GSA-RM1 is determined by the “personality code” selected by the installer, which is downloaded to the module the Signature loop controller during system configuration.

Zalo

Consulting hotline: 0944934114
Product information

- Depending on their assigned personality, Riser Monitor Modules may be used to monitor telephone risers or 70 Vac audio, 25 Vac audio, or 12 Vdc to 24 Vdc risers.

- Upon the loss of a signal, the fire alarm control panel indicates an alert status. The Riser Monitor Module requires one module address

Standard Features

• Adjustable time delay

- 0 - 75 seconds (default 15 seconds)

• Monitors audio power or telephone risers

- Reports a trouble condition when voltage on the riser drops below the trouble threshold.

• Plug in (UIO) or standard 2-gang mount

- UIO versions allow quick installation where multiple modules are required. The 2-gang mount version is ideal for remote locations that require a single module.

• Automatic device mapping

- Signature modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop.

• Electronic addressing

- Programmable addresses are downloaded the loop controller, a PC, or the SIGA-PRO Signature Program/Service Tool. There are no switches or dials to set.

• Intelligent device with microprocessor

- All decisions are made at the module to allow lower communication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties; twisted or shielded wire is not required.

• Non-volatile memory

- Permanently stores serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, and time and date of last event.

Application

The GSA-RM1 mounts to a standard North American two-gang electrical box, making it ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module

Installation

The GSA-RM1: mounts to North American 2-1/2 inch (64 mm) deep 2-gang boxes and 1-1/2 inch (38 mm) deep 4 inch square boxes with 2-gang covers and GSA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2 ) wire size.

Typical Wiring (GSA-RM1)

Modules will accept #18 AWG (0.75mm2 ), #16 (1.0mm2 ), #14 AWG (1.50mm2 ) and #12 AWG (2.50mm2 ) wire sizes. Note: Sizes #16 AWG (1.0mm2 ) and #18 AWG (0.75mm2 ) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

Riser Monitor Modules GSA-RM1

Specifications

Mounting (GSA-RM1) North American 2½ inch (64 mm) deep 2-gang box; 1½ inch (38 mm) deep 4 inch square box with 2-gang cover and GSA-MP mounting plates
Mounting (GSAMRM1) Plugs UIO2R, UIO6R or UIO6 Motherboards
Current

Standby

Activated

200 µA

200 µA

Maximum Input

Voltages

Riser monitor

12 Vdc + 15%

24 Vdc + 15%

25 Vac + 15%

70 Vac + 15%

28 Vdc

Telephone

Input Currents

12 Vdc

24 Vdc

25 Vac

70 Vac

Telephone 24 Vdc

10 mA dc

10 mA dc

10 mA rms

10 mA rms

20 mA dc

Riser loading

70 Vac

25 Vac

24 Vdc

12 Vdc

Telephone

Z > 11k Ohm

Z > 1k Ohm

R > 2.4k Ohm (2 amps)

R > 1.2k Ohm

R > 1.2k Ohm,

Z > 1.2k Ohm

Trouble Threshold Approximately 25% of riser input
Wiring Terminations Suitable for #12 to #18 AWG (2.5 mm² to 0.75mm²)
Personality Codes Two Selectable Codes Available
Address Requirements Uses One Module Address
Operating Voltage 15.2 to 19.95 Vdc
Construction High Impact Engineering Polymer
Storage and Operating Environment

Operating Temperature: 32° F to 120° F (0° C to 49° C)

Storage Temperature: -4° F to 140° F (-20° C to 60° C)

Humidity: 0 to 93% RH

LED Operation

On-board Green LED - Flashes when polled;

On-board Red LED - Flashes when in alarm/active

Compatibility Use With: Signature Loop Controller
Agency Listings UL, ULC, MEA, CSFM

Ordering Information

Catalog Number Description Ship Wt. lbs (kg)
GSA-RM1 Riser Monitor Module (Standard Mount) - UL/ULC Listed 0.5 (0.23)
GSA-MRM1 Riser Monitor Module (Plug-in) - UL/ULC Listed 0.18 (0.08)

 

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about Riser Monitor Modules GSA-RM1

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.15172 sec| 4340.734 kb