Intelligent Addressable Fixed Temperature Heat Detector KI-HFD
KI-HFD Fixed Temperature Heat Detector ⭐✅ provides a 135
°F (57
°C) fxed-temperature heat sensor for the detection of heat due to fre. The heat sensor monitors the temperature of the air and determines whether an alarm should be initiated.
The KI-HFD is an intelligent fixed-temperature heat detector that contains a fixed-temperature heat sensor rated at 135 °F (57.2 °C). It does not have a rate-of-rise function. The heat sensor monitors the temperature of the air in its surroundings and the detector analyzes the data to determine when the air temperature near the detector exceeds the device’s alarm point.
Standard Features
Note: Some features described here may not be supported by all control systems. Check your control panel’s Installation and Operation Guide for details.
• Next generation heat sensing technology
• 135 °F (57 °C) fixed temperature alarm point (HRD and HFD)
• 15 °F (8.3 °C) per minute rate-of-rise alarm point (HRD)
• Uses existing wiring
• Automatic device mapping
• Sensor Markings Provide Easy Testing Identification
• Up to 250 total devices per loop
• Non-volatile memory
• Electronic addressing
• Bicolor (green/red) status LED
• Cover marking for easy identification during testing
• Standard, relay, fault isolator, and audible mounting bases
• 50 foot (15.2 meter) spacing
Application
The KI-HFD combination fixed temperature/rate-of-rise heat detector provides a 15 °F (9 °C) per minute rate-of-rise heat sensor for the detection of fast-developing fires, as well as a 135°F (57°C) fixed temperature sensor for slow building-fires. The KI-HFD fixed temperature detector provides a 135°F (57°C) fixed temperature sensor for slow building-fires.
Isolator Detector Base, KI-IB, KI-IB4
This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate. The isolator base does not support the GSA-LED Remote LED.
The isolator operates as follows:
- a short on the line causes all isolators to open within 23 msec
- at 10 msec intervals, beginning on one side of the class A circuit nearest the loop controller, the isolators close to provide the next isolator down the line with power
- when the isolator next to the short closes, it reopens within 10 msec.
The process repeats beginning on the other side of the loop controller.
Relay Detector Base, KI-RB, KI-RB4
This base includes a relay. Normally Open or Normally Closed operation is selected during installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s position is supervised to avoid accidentally jarring it out of position. The KI-RB can be operated as a control relay if programmed to do so at the control panel. The relay base does not support the GSA-LED Remote LED.
Audible Sounder Bases, Fire Mode ABDT, ABST, ABLT sounder bases
Dimensions
Specifications
KI- HRD | KI-HFD | |
Operating voltage | 15.20 to 19.95 VDC | |
Normal operating current | 51 µA | |
Alarm current | 68 µA | |
Vibration level | 10 to 35 Hz, with an amplitude of 0.01 in. | |
Rate-of-rise rating | 15°F/min (8°C/min) | NA |
Fixed temperature rating | 135°F (57.2°C). Actual alarm point 129 to 141°F (53.9 to 60.6°C) | |
Maximum spacing | 50 ft. (15.2 m) centers | |
Compatible bases | See Ordering Information | |
Compatible detector testers | Testifire 1000, Testifire 2000 | Testifire 2000 |
Operating environment | 32 to 100°F (0 to 38°C), 0 to 93% RH, noncondensing | |
Construction | High Impact Engineering Polymer, White | |
Storage temperature | -4 to 140°F (-20 to 60°C) | |
Agency Listings | CAN/ULC-S530, UL 521 | CAN/ULC-S530-M91, UL 521 |
Ordering Information
Catalog Number | Description | Ship Wt. lbs (kg) |
KI-HRD | Intelligent fixed temperature/Rate-of-rise heat detector | 0.4 (0.16) |
KI-HFD | Intelligent fixed temperature heat detector |
Compatible Bases
KI-SB | Detector Mounting Base - Standard | 0.2 (.09) |
KI-SB4 | 4-inch Detector Mounting Base c/w Trim Skirt | |
KI-RB | Detector Mounting Base w/Relay | |
KI-RB4 | 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt | |
KI-IB | Detector Mounting Base w/Fault Isolator | |
KI-IB4 | 4-inch Detector Mounting Base w/ Fault Isolator, c/w Trim Skirt | |
KI-ABST | Audible (Sounder) Base for Fire Detectors | 0.3 (0.15) |
KI-ABLT | Low Frequency Audible (Sounder) Base for CO and Fire Detectors | |
KI-ABDT | Audible (Sounder) Base for CO and Fire Detectors | |
GSA-LED | Remote Alarm LED (not for EN54 applications) | |
GSA-TS4 | Trim Skirt (supplied with 4-inch bases) | 0.1 (0.04) |
GSA-TS | Trim Skirt (optional for non 4-inch bases) |