VK377 Storage Sprinkler viking Specifications

VK377 Storage Sprinkler viking

- Maximum working pressure: 175 psi (12 bar).

- Factory hydrostatically tested to 500 psi (34.5 bar).

- Reading Size: See Approval Chart

- K-factor : 11.2 US (161.3 meters )

- Glass bulb liquid temperature rated to -65°F (-55°C)

- Overall length: 2 -5/16 (58.7 mm)

- The K-factor measurement is measured when the pressure is measured in Bars. When the pressure is measured in kPa, divide the display coefficient K factor by 10.0.

Standard List of Nozzles Archives VK377

- CULus listed: VNIVFM approved class: Class 2009

- VdS Approved: Certificate G413049, G413051LPCB Approved:

- Certificate of 096e/14Refer for Approval Chart and Design Criteria for the requirements to be followed.

The VK377 Storage Nozzle is an extra-large sprinkler with heat-resistant glass ball available in a number of different finishes and temperature ratings to meet design requirements. Special coatings Polyester and Electroless Nickel PTFE (ENT) can be used in decorative applications where color is desired.

In addition, the VK377 Storage Nozzles covered with these coatings have been studied for installation in corrosive environments and are listed/approved as outlined in the Approval Chart. Extra large holes provide greater flow at lower pressure than standard orifice or large hole sprinklers. This feature allows to reduce pipe sizes for hydraulically calculated sprinkler systems that require high water densities. The quick response of the VK377 extra large water jet can eliminate the need for a fire pump or reduce the size of the pump if necessary. On existing systems, replacing large bore sprinklers with extra large bore nozzles can provide the higher densities needed to allow for increased hazard classification of occupancy. The quick response nozzle can be used as an open nozzle (glass bulb and pip cap assembly) on deluge systems.

Installation instructions for the VK377 . Archive Nozzle

 

VK377 Storage Sprinkler viking

VK377 Storage Sprinkler viking

VK377 Storage Sprinkler viking

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about VK377 Storage Sprinkler viking

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.64801 sec| 4322.5 kb