Viking VK901 Fire Sprinkler, Viking VK100 VK102 Vk104
Factor K4.2 Quick Response, Uprght Style, Brand 12 months nationwide warranty The best type of fire extinguishing nozzle available today... Contact 0917911114 to get a quote for VK100,VK102 nozzles, VK104, Vk200
The Viking VK901 Fire Nozzle (Viking QR COIN®) is a fast-responsive, application-specific nozzle for interstitial (concealed) spaces (i.e. between floors, as well as low attic floors that respond to pccc criteria). The Viking VK901 vertical sprinkler head is designed for use in flammable light hazards, as well as non-combustible concealed spaces where sprinkler protection is required.

The Viking QR COIN® Sprinkler's orifice design, with a nominal K-Factor of 4.2 (57 meters), allows efficient use of available water supplies for fire protection systems. The fire is hydraulically designed. The fusible-bonded operating element and special deflector combine operating speed and coverage area to meet the critical fire protection requirement for flammable space concealment spaces.
Technical information Viking Fire Sprinkler VK901
- Minimum operating pressure: Refer to Design Criteria.
- Rated to 175 psi (12 bar) water working pressure
- Hydrostatically tested to 500 psi (34.5 bar) Test: US Patent No. 4,831,870 - Reading size: 1/2, (15 mm) NPT
- Nominal K-Factor: 4.2 US (57 metric )
The K-factor measurement displayed is when the pressure is measured in Bar. When the pressure is measured in kPa, divide the K-factor by the factor displayed by 10.0.
- Medium length: 2-1/4” (57 mm)
Installation diagram of Viking VK901 . Fire Sprinkler