Technical Data Sprinkler Viking VK 604
Independent Response Type (Including standard and rapid response)
Vertical Style Pendent
Minimum operating pressure: Refer to Approval Chart.
Maximum working pressure: 175 psi (12 bar) Factory hydrostatically tested to 500 psi (34.5 bar).
Check: US Patent No. 4,831,870 Reading Size: 1/2, (15 mm) NPT Factor K-Factor: 5.6 US (80.6 metric )
The K-factor gauge displayed is when the pressure is measured in Bars. When the pressure is measured in kPa, the K factor by the coefficient shown gives 10.0. The bulb's liquid temperature is rated as -65°F (-55°C) Overall Length: 2-1/4 (58 mm)