Monitoring module for conventional detector Hochiki DCP-CZM

Manufacture: INGESCO
Product code: DCP-CZM

Monitoring module for common detector Hochiki DCP-CZM Genuine Hochiki _ Taiwan , Best price in the market , Long-term warranty ,Commitment to nationwide delivery , Contact : 0917911114

Zalo

Consulting hotline: 0944934114
Product information

Monitoring module for conventional detector Hochiki DCP-CZM

General features: DCP- CZM . conventional detector monitoring module

– Addressing a zone of 25 conventional smoke detectors.
– Normally, the green light flashes. When activated, the light turns red.
– The address can be programmed (1 to 127) using a programming device (programmer).
– Suitable wiring according to Class B or Class A.
– Use the power supply for the smoke detector zone. Compatible with conventional detectors of the SLR, SIJ, SLK and SIH series.
 
Description: DCP-CZM . conventional detector monitoring module
 
The CZM module is designed for use in FireNet addressable fire alarm systems. Up to 127 addressable devices can be connected per SLC loop. The address of the device is stored in the EEPROM of the main board. This module allows the control panel (panel) to communicate and monitor dry contacts such as conventional 2-wire smoke detectors or emergency switches. Each CZM is addressed through the control cabinet and transmits a signal to the panel, indicating the operating status of a zone (up to 25 devices can be connected per zone). It monitors the source as well as all devices in the zone. The reported states include: normal, open circuit, or alarm. UL approved class 2 smoke detectors are CZM compatible. By means of digital communication (DCP) combined with high reliability and fast transmission speed, CZM is ready to respond effectively in case of emergency. The module has an LED (dual color) to show its operating status.
 
Specifications: Normal detector monitoring module DCP-CZM
 
– Operating voltage 17~41 VDC
– Auxiliary power voltage 18.8 ~ 27.2 V
– Average current (S-SC) 400 A
– 2 wire detector circuit current 1mA Max.
– Alarm auxiliary source (short circuit of detector line) 60mA Max.
– Data transfer current 22 mA ± 20%
– Resistor at the end of the line 4.7 K Ohms
– Alarm threshold < 1.5K Ohms – OK wire threshold >2.5K Ohms & <6K Ohms
– Open circuit threshold > 10K Ohms
– Conventional circuit breaker type 2 wire 50 Ohms (total SLC line length)
– Operating temperature 0˚ ~ 49˚C
 
Installation characteristics: Normal detector monitoring module DCP-CZM
 
– The CZM module can be equipped and placed wherever it is needed according to the plan. This module is compatible with Hochiki America's Analog Fire Alarm Panel protocol. The address of the device is set by the electrical device and stored in the EEPROM. LEDs (dual color) are used to show the operating status of the device.
– CZM is equipped with a plastic container cover, suitable for installation in a 4” square box

For good prices and technical advice on Monitoring Modules for Hochiki DCP-CZM conventional detectors and related products to addressable fire alarm systems and conventional fire alarm systems, please do not hesitate to contact us for information. under ! See more fire alarm bases here

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..