DCP-CZM: Module for use with conventional detectors
Module cho đầu báo thường CZM (Thiết Bị Báo Cháy Hochiki)
Provides one address for an area where up to 25 conventional fire alarms are installed. Led flashes blue when working. The LED lights up continuously in red (controlled by the control panel) when activated. The device address can also be programmed with a handheld programmer. Device address, range 1-127. Compatible with Class B (style B) and Class A (style D). Auxiliary power supply for the area with common fire alarm devices. Specifications Supply voltage (S-SC): Loop voltage (Low) 17-31 VDC Auxiliary power voltage: 19-30 VDC Average current consumption: (S-SC) 400µA . Monitoring Mode Loop current consumption of 2-wire detectors: Standby (CZM + 25 detectors + EOL) 5mA Max Current Consumption Auxiliary Power Alarm 60mA Max Current consumption when transmitting data 22mA ± 20% End resistor 4.7K Ohms Alarm Impedance 2.5K Ohms & 10K Ohms
The maximum number of detectors is usually 25
Operating temperature: 0°C - +50°C
Storage temperature: -30°-+60°C