Descriptions HCV Hochiki Fire Alarm Center 2 4 8 channels
Fire alarm center 2/4/8 channels: HCV-2, HCV-4, HCV-8
HCV cabinet series includes 2,4,8 zones, designed in accordance with BS EN54-4, BS EN54-2 standards and fire alarm system - control and indicator equipment. The HCV series of cabinets has a combination of power and battery charging circuit. The cabinet has voltage-free contacts for the Fire and Local Fire ports that activate every time a fire event occurs. They are used for control and signal transmission. Complies with BS EN54-4 standard. The HCV series of cabinets are fully programmed through a simple selection menu. The cabinet has a single-circuit structure, which is easy for people to install. Compatible with a wide range of devices. Remote control via inputs, allowing: alarm mute, chime, fault alarm and reset.
Specifications HCV Hochiki Fire Alarm Center 2 4 8 channels
Power supply: 120VAC (50hz/60hz) or 220VAC (50hz/60hz)
Working voltage, supply current :24V 3
Amps Mains fuse: 1.6 Amp 250V
Dimensions: 385mm(W) x 310mm(H) x 92mm(D)
Weight: 11.5 lbs.
Color: Red Material 1.2mm mild steel Battery size up to 7Ah 12V (2 /cabinet)
Fault contact 30VDC 1
Amp Local Fire Contacts 30VDC 1
Amp Fire Contact 30VDC 1
Amp NAC output current 0.5A per input (maximum 1.6A for all outputs) Input current zone 1.6mA End-of-line resistance zone 6K8 5% Ring end resistance 10K 5% Static current HCV-2: 0.065Amp, HCV-4: 0.075Amp, HCV-8: 0.093Amp Alarm current HCV-2: 0.1Amp, HCV-4: 0.21Amp, HCV-8: 0.55Amp Cable size to connect to cabinet 2.5 mm 95% working humidity (no condensation) Working temperature -5°C to +50°C
Have 0 comment, evaluate about HCV Hochiki Fire Alarm Center 2 4 8 channels
TVAdministratorsAdministrators