· Compliant with UL 864 9th edition.
· Open to supervision by contact Fast, highly reliable contact monitoring using DCP (Digital Communications Protocol) protocol.
· Up to 127 devices can be installed on 1 DCP loop.
· Normally open NO or normally open supervision can be programmed.
· Type A or B installation.
Specifications
Power Supply (S-SC) 25.3 ~ 39 VDC
Current Consumption 630μA (Typical) 6.3mA (Alarm)
SCI isolating trigger resistor 40m ohm
Max. (Normal Condition) SCI isolation fault detection threshold 12 volts (Typical)
Short Circuit Condition 10mA (Typical)
Maximum number of devices per 1 Loop 127
Dimensions 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32 0F (0 0C) ~ 120 0F (49 0C)
Carrying case for installation
Power Box 4"
Relative humidity 90% RH Non-condensing