VK482 Quick Response Drying Nozzle
Price list for fire extinguishers (50%)
VK482 : Quick Response Drying Nozzle is a small high sensitivity elemental sprinkler designed for installation on concealed duct systems where the appearance of a smooth ceiling is required. The sprinkler hole design, with a K Factor of 5.6 (80.6 meters), allows the sprinkler to efficiently utilize the water supplies available to the hydraulically designed fire suppression system. The two-piece design of the sprinkler and escutcheon allows the sprinkler to be installed and tested prior to ceiling installation. The Ecutcheon allows for vertical adjustment up to 3/4 (19.5 mm) and can be removed and reinstalled, allowing access to removable ceiling panels without shutting down the sprinkler system. and remove the sprinkler head.
Detailed description of VK482: quick response dry spray head
- Minimum operating pressure: 7 psi (0.5 bar)
- Maximum working pressure: 175 psi (12 bar).
Factory hydrostatically tested to 500 psi (34.5 bar).
Reading Size: 1 K N (25 mm)
- K-factor : 5.6 US (80.6 meters ) The K-factor measurement displays in the Bar. When the pressure is measured in kPa, divide the K-factor by the factor displayed by 10.0. Covered by the following US Patents: 8,636,075