Contact Relay Module FX-RLY
The FX-RLY provides one Form C dry relay contact. It can also be configured to provide polarity reversal of its output ⭐
✅ The FX-RLY can be used to control external appliances or shut down equipment.
- The FX-RLY is wired according to its operation. It is configured to operate as a relay nonsilence device type, and can function as either a control relay or polarity reversal relay, depending on how it is wired.
- Control relay function: Provides one Form C dry relay contact.
- Polarity reversal relay function: Provides polarity reversal of its output.
Note: Additional device types are available through front panel programming or the configuration utility. Refer to applicable control panel technical reference manual.
| Communication line voltage | Maximum 20 V peak-to-peak |
| Current | |
|
Standby Activated |
125 µA 125 µA |
| Contact ratings (pilot duty) | |
|
30 VDC 125 VAC |
2 A 0.5A resistive load 60 W or 62.5 VA max |
| Relay type | Form C, programmable |
| Ground fault impedance | 10 k ohm |
| Operating environment | |
|
Temperature Humidity |
32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing at 90°F (32°C) |
| Storage temperature range | –4 to 140°F (–20 to 60°C) |
| Compatible electrical boxes | North American 4 inch square x 2-1/2 in. (64 mm) deep 1 gang box North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep box |
| Wire size | 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred) |
| Module address (one address required) | 01 to 64 (64 point control panel) 01 to 127 (1000 point control panel) |
Ordering Information
| Model | Description | Ship Weight |
| FX-IDC1A | Analog Class A Single Input Module | 0.50 lbs. (0.23 kg.) |
| FX-IDC1B | Analog Single Input Mini Module | 0.34 lbs. (0.15 kg.) |
| FX-2WIRE | Analog Class A-B Two-Wire Module | 0.50 lbs. (0.23 kg.) |
| FX-IDC2B | Analog Dual Input Module | 0.50 lbs. (0.23 kg.) |
| FX-2IDCWS | Analog Dual Input Waterflow-Supervisory Module | |
| FX-NAC | Analog NAC Module | |
| FX-RLY | Analog Contact Relay Module | |
| FX-ISO | Analog SLC Fault Isolator Module |