Unipos interactive fire alarm cabinet IFS7002 - 1 loop
The IFS 7002 Interactive Fire Control Panel is an up-to-date, highly reliable, multifunctional and versatile device that offers users unexpected potential in the design, installation and operation of alarm systems. address fire.
PRODUCT DESCRIPTION
The IFS 7002 Interactive Fire Control Panel is an up-to-date, highly reliable, multifunctional and versatile device that offers users unexpected potential in the design, installation and operation of alarm systems address fire.
SPECIFICATIONS:
Physical configuration:
- 1 fire alarm ring
- 2 supervised outputs
- 1 relay output for fire condition
- 1 programmable relay output for fire condition
- 1 relay output for fault conditions Fire alarm zone: - Area code max - 64
- Maximum number of fire detectors and input devices
- 60 Fire alarm rings: - Maximum number of fire detectors in a loop - 125
- Connection line - protected by two wires
- Maximum loop resistance - 100
- Output resistance of the loop - 20
- Maximum loop consumption - 200mA Monitored output: - 2 pcs
- Type - potential
- Picture Characteristics - (24 ± 5) V / 0.5A Relay output for fire conditions
- 1 pc - Type - potential free, switching
- Electrical characteristics - 3A / 125VAC; 3 / 30VDC Relay output (programmable) for fire conditions - 1 pc - Type - potential free, switching
- Electrical characteristics - 3A / 125VAC; 3 / 30VDC Relay output for fault conditions - 1 pc - Type - potential free, switching - Electrical characteristics - 3A / 125VAC; 3 / 30VDC Efficiency: Controls fire alarm loops and monitored outputs for fault conditions (short circuit and interruption) and automatic reset
- Dedicated led indicator for each fire zone - Detects removed devices in loops and resets automatically - Ability to set regions in Matching Mode - Two stages of fire conditions, programmable time for stage I fire conditions, separate for each zone - Extended interval option for stage I fire conditions with programmed test times, assigned to each zone - Built-in sound for fire conditions - one tone, intermittent, can be muted - Built-in audio for fault condition - one tone, intermittent, can be muted - Built-in real-time clock - Set test modes and options for tuning - Clock settings:
- Check the light and sound indicator - Check the fire alarm zone - Adjustable output and built-in external devices - Programmable parameters and operating modes - Remote programming of parameters remote operator's control point - Energy independent event log of registered events with event type, date and time - up to 1023 events - Interface for communication with external devices - CAN 2.0B and USB. Indicator of registered events: - Light indicator - LED - Text messages - LCD display, 320 240 dots, backlight - Audio signal - built-in audio Electricity supply: Source electricity :
- voltage - 220 / 230V - frequency - 50Hz Battery backup: - battery type - lead, gel electrolyte - number of batteries - 2 pcs - connection - serial connection - rated voltage of backup battery - 2x12V DC - nominal capacity C20 - 7Ah - charging voltage - 28V Consumption when supplying backup battery: - at 24V - <160mA - at 26V - <150mA Powering external devices: - Voltage - (24 ± 5) volts - Maximum current value (including monitored output current) - 1iano Size: - Overall dimensions - 286 x 148 x 125 mm - Weight (excluding battery) - 1,240 kg.
You can refer to products genuine fire alarm equipment...HERE