The Tyco upward sprinkler sprinkler TY6137 belongs to the EC-14 series of standard response type wide-coverage sprinklers with a flow rate of K=14.0. They are designed for use in low or general hazardous environments. In addition, they are also used for automatic sprinkler fire suppression systems, allowing installation in buildings with open ceilings or difficult to fire according to installation standard NFPA 13.

Technical information of the sprinkler head sprinkler Tyco upward TY6137
- Meet standards: UL, C-UL, FM
- Maximum working pressure: 175 psi (12.1 bar).
- Spray flow: K=14.0 GPM/psi½ (201.6 LPM/bar½).
- Nozzle size: 3/4 inch NPT (DN20).
- Activation temperature:
+ 135°F (57°C) Orange glass tube
+ 155°F (68°C) Red glass tube
+ 175°F (79°C) Yellow glass tube
+ 200°F (93°C) Green glass tube
+ 286°F (141°C) Blue glass tube
- The maximum coverage area is up to 37.2 m², larger than the specified 12.1 m2 in normal hazardous environments and 20.6 m2 in mildly hazardous environments.
- TY6237 has a protective coating that prolongs the life of the nozzle when using the nozzle in corrosive environments.
- Plating material: Brass, Cr.
Have 0 comment, evaluate about Tyco Upright Sprinkler TY6137