Tyco Pendent Sprinkler Ty6237
Tyco Pendent Sprinkler Heads Ty6237, Approval: UL, C-UL, NYC, FM, Tyco Pendent Sprinkler Heads TY6237 are part of the standard response, EC-14 family of products. Designed for use in low or normal hazardous environments.

Tyco downward sprinkler sprinkler head TY6237
- Product line: EC-14 - Spray coefficient: K=14.0
- Size of glass tube: 3mm
Description of Tyco Pendent sprinkler sprinkler head TY6237
- Apply for:
+ Low or normal hazardous environments.
+ Automatic sprinkler fire extinguishing systems, allowing installation in buildings with open ceilings or difficult to burn according to installation standards NFPA 13.
- The maximum coverage area is up to 37.2 m², larger than the specified 12.1 m2 in normal hazardous environments and 20.6 m2 in mildly hazardous environments.
- Has a protective coating to prolong the life of the nozzle when using the nozzle in corrosive environments.
- Plating material: Brass, Cr.
Technical data of Tyco Pendent sprinkler sprinkler head TY6237
- Meet standards: UL, C-UL, FM
- Maximum working pressure: 175 psi (12.1 bar).
- Injection coefficient: K=14.0 GPM/psi½ (201.6 LPM/bar½).
- Nozzle size: 3/4 inch NPT (DN20).
- Activation temperature: + 135 °F (57 °C) Orange glass tube
+ 155 °F (68 °C) Red glass tube + 175 °F (79 °C) Yellow glass tube
+ 200 °F (93 °C) Green glass tube + 286 °F (141 °C) Blue glass tube