Tyco Ceiling Nozzle Ty3200
TY3200 FSC series of fast response nozzles Ceiling nozzles K-factor 5.6 MF200 system quote FM200 fire fighting system installation consultation 100% Tyco brand Long-term warranty Hotline 0917911114 receive Quotation and technical advice
The TY3200 ceiling mounted Tyco nozzle belongs to the FSC series of quick-response nozzles, with standard coverage with a spray coefficient of K=5.6. The TY3200 nozzle is designed to be suitable for use in areas with ceilings or concrete floors, false ceilings with high aesthetic requirements such as office apartments, hotels, hospitals, churches, schools, ..
Specifications of Tyco ceiling nozzle TY3200
- TY3200 meets VDS standard for installation according to CEA 4001 “Sprinkler Systems: Planning” and EN12845 “Fixed Firefighting Systems - Automatic Sprinkler Systems
- Design, Installation and Maintenance”.
- Maximum working pressure: 175 psi (12.1 bar).
- Injection coefficient: K=5.6 GPM/psi½ (80.6 LPM/bar½). Operating temperature: 74°C (165°F).
- When using the nozzle in the ceiling or concrete floor, a special "cup" is required in the recess of the cavity to install the nozzle.
- Has a dustproof cap, good protection for the nozzle
- Available in 2 colors: white and gray
You will receive a quote from us as soon as possible..