Sprinkler Tyco Model ESFR 1 TY6226

Manufacture: Tyco
Product code: Model ESFR 1, TY6226

manual for horing fire alarm center ah-00212 Combination of 5-channel 10 channel Horing fire alarm cabinet Horing ah-0311-2 smoke detector combined with Horing fire alarm QA16  Model ESFR 1,TY6226, K=14.0 Pendent Sprinkler

Zalo

Consulting hotline: 0944934114
Product information

Đầu phun Sprinkler Tyco Model ESFR 1 TY6226

Đầu-phun-Sprinkler-Tyco-Model-ESFR-1-TY6226

K-factor 14 Direction type: Face down

Đầu phun Sprinkler Tyco Model ESFR 1 TY6226

SlopeMaximum 2 in.12 in (16.7%) Coverage up to 100 ft2 (9.3 m2) In some cases, installed stan-dards allow a larger coverage area. Minimum coverage area of 64 ft2 (5.8 m2) per NFPA 13 / FM 2-0Maximum Spaces12 ft (3.7 m) for building heights up to 30 ft (9.1 m) 10 ft (3, 1 m) for building heights greater than 30 ft (9.1 m) Minimum clearance 8 ft (2.4 m) Minimum cargo clearance36 in. (914 mm) Ceiling-to-ceiling DistanceNFPA - 6 in to 14 in. (152 mm to 356 mm) Ceiling-to-ceiling heat sensing element centerline FM 2-0 for Sprinklers Store.