Specifications Orbis Apollo ORB OP 52028 APO Optical Smoke Detector
Aplications |
Dusty environment Escape routes Dangerous area Offshore platforms Oil factory Small and medium buildings |
Longevity | 10 years |
Chamber type | Chevron |
Maximum Power On Time Quiet Stream Static Current Tested At Sampling Frequency Polarity Minimum 'Active Detector' Voltage Hold Voltage (Min.) Minimum Voltage for LED Alarm to Light Voltage Reset Alarm Alarm Reset Time Download Alarm |
<20 second 85μA 24V dc Every 4 secondsL1 & L2 are polarity sensitive 12V 5V 6V <1V 1 second 325Ω in series with 1.0V drop |
Humidity (Min.) Humidity (Max.) Rated Value Storage Temperature (Min.) Storage Temperature (Max.) Storage temperatures |
0% RH 98% RH IPIP23D -40 ° C 70 ° C -40 to 70 ° C |
Approve |
BV LR LPCB KRS IECEx FG DNV.GL BASEEFA BOSEC CCS SBSC CPR PESO (CCoE) ABS |
Weight Color Material Product Length Product Diameter Detection Principle Sensor Configuration |
75g White Polycarbonate 42mm 100mm Electro-optical light scattering. Chamber with surface mount prism and infrared generator. Solid-state integrated amplifier and photodiode. |
You can refer to products genuine fire alarm equipment...HERE
Have 0 comment, evaluate about Orbis Apollo ORB OP 52028 APO Optical Smoke Detector
TVAdministratorsAdministrators