Optical Smoke Detector XP95 IS, Apollo 55000-640APO
55000-640APO The optical smoke detector incorporates a pulsed LED located in a maze inside the detector's housing
⭐The maze is designed to exclude light any external source. At an angle to the LED is a photodiode that, in clear air, receives no direct light the LED.
Specifications
Applications Fire Type Longevity |
Escape routes Dangerous area The building is medium to large Offshore platforms Oil factory Slow fire, smoldering fire 10 years |
Protocol Voltage Protocol Voltage Protocol Voltage Quiet Stream Static Current Tested At Polarity | (Min.)5V (Max)9V 5 to 9V peak to peak 340μA 24V dc L1 & L2 are polarity sensitive |
Humidity (Min.) Humidity (Max.) Notes About Humidity Humidity |
0% RH 95% RH does not condense or freeze 0% to 95% (does not condense or freeze) |
Approve |
BV SBSC BASEEFA BOSEC BRZ CCS KRS LPCB LR PESO (CCoE) IECEx NANIO DNV.GL RINA ABS MED CPR |
Weight Colour Material Product Diameter Detection Principle Sensor Configuration |
105g trắng Polycarbonate 100mm Photoelectric light scattering. Horizontal optical bench with IR emitter and sensor, radially arranged to detect front scattered light. |
You can refer to products genuine fire alarm equipment...HERE
You will receive a quote from us as soon as possible..
Have 0 comment, evaluate about Optical Smoke Detector XP95 IS, Apollo 55000-640APO