Nohmi FRRU004-CIZM4 Area Monitoring Module
The common zone monitoring module (FRRU004-CIZM4)is used to monitor the status of common initiating devices connected on , Initiating device circuit (IDC). The FRRU004-CIZM4 detects an alarm condition and reports it to the Fire Alarm Control Panel (FACP). The FRRU004-CIZM4 Modules also supervise the starting device wiring (wires A+, A-, B+ and B-) and wiring for the power connected to terminals 24+ and 24- for output open circuit current ,
IDC wiring pattern is applicable to NFPA Class B (Type B) & Class A (Type D). When the FRRU004-CIZM4 Module detects an alarm, the module is latched until the system resets. When the FRRU004-CIZM4 module is used with Wiring Condition Class A (Type D) and an open circuit is detected on the wire of the IDC and the power is connected to terminals 24+ and 24-, the module is is also latched until the system resets.
Basic Features Nohmi FRRU004-CIZM4 Area Monitoring Module
• A simple LED for status indication
• NFPA Class A (Style 6 & 7) and Class B (Type 4) for SLC
• NFPA Class A (Type D) and Class B (Type B) for IDC
• Set up electronic address
• Size reduction unit
• Easy to install
Specifications Nohmi FRRU004-CIZM4 Area Monitoring Module
| No | Item | Parameter |
| 1 | SLC input rated voltage range (S+,S-) | 22.0 to 24.0V |
| 2 | Maximum SLC 24VDC Standby Current (S+,S-) | 250µA |
| 3 | 24 VDC maximum SLC alarm current (S+,S-) | 1mA |
| 4 | Voltage of the external power supply line (24+,24-) | 24V |
| 5 | IDC output voltage range (A+,A-,B+,B-) | 15.7 to 22.6V |
| 6 | IDC Module Maximum Standby Current 24VDC (24+,24-) | 8.5mA of type B, 4.9mA of type D |
| 7 | Maximum detector standby current IDC 24VDC (24+,24-) | 2.4mA |
| 8 | Alarm current IDC 24VDC max. Module and detector (24+,24-) | 50.0mA |
| 9 | IDC wiring style is applied | Class A (style D), class B (style B) |
| 10 | Maximum wire resistance of IDC | 100Ω |
| 11 | IDC max wire power | 1µF |
| 12 | End-of-line power for IDC in NFPA Type B wiring | 5.1kΩ, 1/2W |
| 13 | Maximum warning voltage | 0V |
| 14 | Minimum reset time | 1.1 s |
| 15 | Working temperature | 0°C to 49°C (32°F to 120°F) |
| 16 | Himidy | 0 đến 93% (non-condensing) |
| 17 | Size | 106mm (4.17 inches) (Cao) × 106mm (4.17 inches) (Rộng) × 29mm (1.14 inches) (Dài) |
| 18 | The box applies to the installation |
64mm (2-1/2 inch) deep 2 cast iron box in North America Standard 4 inch square box 38mm (1-1/2 inch) deep box |