The Kidde Fire Systems Natura™ Inert Gas System provides flexibility with your choice of four agents, efficient installation and overall lower total cost of ownership driven by reduced material, installation and labor costs, as well as a more economical refill cost after a discharge.
Compared with other high-pressure inert gas systems, our series 400 valve regulates flow and pressure to allow the use of Schedule 40 piping for many applications. Installation time and labor costs are further reduced with the use of pre-fabricated manifolds, quick-connect actuation hoses and electrical connectors.
System Benefits
Flexibility
- Choice of four NFPA and ISO approved agents to suit re-charge conditions and customer specifications
- Wide flexibility when selecting storage area as cylinders can be stored hundreds of feet hazard
- Argon may be used for application-specific Class D materials such as titanium dust, magnesium, etc.
- Suitable for low-temperature applications
- Suitable for rooms that are hard to seal and open spaces such as museums and labs
Lower Material Costs
- Pressure and flow regulating valve allows for Sch. 40 pipe
- Actuation up to 60 cylinders accomplished with a single release unit mounted on the primary cylinder so there is no need for separate pilot cylinders
- Selector valves protect multiple hazards with a single cylinder bank, reducing overall system cost
Lower Installation, Labor and Refill Costs
Several sizes of pre-fabricated manifolds with pre-installed check valves ready for discharge hose connections
Fast & easy installation using quick-connect actuation hoses and electrical connections
Economical agent refill cost after a discharge
Why choose an inert gas system?
Safe for the Environment. Pure Inert gases and the constituents of the blended versions are found naturally in the atmosphere. These gases are environmentally responsible, having an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of zero. At room temperature, inert gases are colorless and odorless.
Safe for Human Exposure. In occupied areas, people can breathe Inert gas blends at extinguishing concentrations below 52% for very brief periods of time during egress. There are no toxicological factors associated with the use of Inert gases as they will not decompose or produce any by-products when exposed to a flame.
Features
Cylinders available in 300 bar and 200 bar pressure options
Cylinders available in 80 liter and 140 liter capacity options
Nozzles available with 360 and 180 degree discharge patterns
Cylinders suitable for storage at temperatures -4° to 130°F (-20° to 54°C)
Non-conductive – suitable for electronic equipment protection
Technical Specifications
Actuate up to 60 cylinders with single electric actuator.
Can be used with selector valves to protect multiple hazards a single cylinder bank.
Vent requirements equivalent to chemical clean agents due to flow controlled valve.