MAD-432-I, 24V Detnov Dual Output Addressable Control Module
Addressable control module with built-in isolator with 2 monitored 24V outputs
✔️ for triggering audio-optical signaling systems or operations requiring power, distinguishing tripping or short-circuiting faults in said line ,It occupies two loop addresses ,Requires 24 Vdc auxiliary power supply. Includes status LEDs, Connect via removable strips up to 2.5mm2 cross section. Possibility of mounting on a DIN rail or on a flat wall in a BOX-ONE box. Consumes less than 300μA at idle. Red. Dimensions 100 x 82 x 23 mm. Certified CPR EN 54-18 and EN 54-17.
°Easy to install, allows mounting to surface or DIN rail
° Non-polarity support (MAD-431 and MAD-432 only)
° Addressable by programmer
°External 24V power supply
°Connection via removable, easy-to-connect strips
° CPR certificate EN 54-18 and EN 54-17
Specifications
Loop feature: Working voltage: Consumption at rest: Consumption in alarm: |
22 to 38VDC <300 µA <3 mA |
Secondary source features: Working voltage: Consumption at rest: Maximum consumption. alarm: |
24VDC <5 mA 1 A |
Output features: Working voltage: Consumption at rest: Alarm maximum consumption: |
24VDC <5 mA 1 A |
Relay connection | 1A @ 30VDC |
Sizw | 100 mm x 100 mm x 23 mm |
Temperature | -10ºC to 70ºC |
Humidity | 95% |
Structure | ABS |
Cetifications | EN 54-18 and EN 54-17 |
No | : 0370-CPR-1864 |
Size