VY is a general fire extinguishing control panel The control panel is designed to be used in conjunction with gas, powder, aerosol, water and other active fire extinguishing systems, The control panel is divided two parts. operation: fire extinguishing and fire fighting, IVY has 3 wire zones - 2 zones activate automatic fire detectors and 1 common fire zone support up to 32 detectors, Automatic and manual operation mode (can be operated) selectable via 3 position key) and a special button for manual execution of quenching, The Control Panel is designed to work with solenoids, pressure regulators and other types of actuators. An optional LOG module can be added to the IVY's configuration to review logged memory events, the IVY Fire Control Panel is designed according to EN12094-1 and EN54-2/4 standards.

Zalo

Consulting hotline: 0944934114
Product information

1. Input specifications:

- 2 Normal zones to put out fire

- 1 Normal Area for Fire Alarm

- Low pressure inlet

- balanced inlet supervised

- Manual release input

- supervised balanced input

- Mode input

- balanced input monitored for switching between Manual and Auto operating modes

- Input hold - balanced input monitored

- On/Off - balanced input monitored

- Flow control - balanced inlet monitored

2. Output specifications:

- SND 1 (Sounder 1) -Monitor, 24VDC, 300mA

- SND 2 (Sounder 2)- Monitor, 24VDC, 300mA

- Relay phase 1 “Fire alarm” (NC, COM, NO), 5-30VDC/1A

- Phase 2 relay “Extinguishable” (NC, COM, NO), 5-30VDC/1A

- Fault relay (NC, COM, NO), 5-30VDC/1A

- Extinguishing output (EN 12094-1), Monitor, 24VDC/1A 5 min, 24VDC/3A 20ms

- OC1 - in case of Hold Trigger - open-collector type

- OC2 - in case of extinguishing disable - open collector type

- OC3 - in case of low pressure - open collector type

- OC4 - in case of manual mode activation - open receiver type

Supply 110-230VAC ± 10%
Frequency 47-60Hz
Backup power supply 2 x 12V / 7Ah
Power consumption 26VDC; 1,5A
Battery Resistance <0,3Ω
Consume 0,3A@230VAC; 0,7@110VAC
Temperature -5 ° C to + 40 ° C
Humidity (93 ± 3)% @ 40 ° C
Dimensions of metal box 324x314x82mm

Please see similar products….HERE

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about IVY, Fire control cabinet for water aerosol powder gas system

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.28149 sec| 4328.211 kb