Tyco horizontal sprinkler sprinkler TY3321 (TYCO Series TY-FRL 5.6K Horizon-Tal Sidewall Sprinklers (HSW)). Quick response, standard coverage are sol-der nozzles designed for use in light and general commercial trades such as banks, hotels, shopping malls, offices, etc.
.gif)
The Tyco horizontal sprinkler head TY3321 is designed for installation along a wall or side of a beam and directly under a smooth ceiling. Horizontal sprinklers are commonly used in lieu of stand-alone or vertical sprinklers due to aesthetic or building construction considerations, where piping in the ceiling is not desirable.

Basic specifications Tyco horizontal sprinkler sprinkler TY3321
- Mounting position: They are designed to be installed along the wall as an alternative to up or down nozzles
- Meets standards: UL, C-UL, FM and NYC
- Maximum working pressure: 175 psi (12.1 bar).
- Injection coefficient: K=5.6 GPM/psi½ (80.6 LPM/bar½).
- Nozzle size: 1/2 inch NPT (DN15).
- Activation temperature:
+ 165°F (74°C) Unpainted
+ 212°F (100°C) White paint
+ 280°F (138°C) Blue paint
The nozzle is coated with an anti-corrosion coating to prolong its service life. However, this does not mean that this nozzle is suitable for all corrosive environments. Therefore, users should contact for advice on the suitability of anti-corrosion materials for each specific environment.