GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

21/04/2022

GST Series Hand Held Programmer, P-9910B / GST-BMQ-1B Hand Held Programmer can read the address, sensitivity and device type and program device type of addressable detectors, modules and repeater panels. The handheld programmer has to be separately ordered

Getting Started

The following is a summary of the basic steps to bring a GST-M200 FACP on-line:

 Install the cabinet (refer to Section 2.1 Installing the Cabinet)

 Connect with addressable devices

 Enter Auto-programming (refer to Section 3.5)

 Define devices (refer to Section 3.4.3) and Event and Command (E&C) equation (refer to Section 3.4.5)

Installation

- The cabinet mounts using three 12mm-diameter holes located in the back box.

- Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel.

- Locate the cabinet at a proper height above the floor with the hinge mounting on the right.

Installing the Cabinet

GST-M200 Intelligent Fire Alarm Control Panel

Installation and Operation Manual

Installation

The cabinet mounts using three 12mm-diameter holes located in the back box.

Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean,

dry, vibration-free area where extreme temperatures are not encountered. The area

should be readily accessible with sufficient room to easily install and maintain the panel.

Locate the cabinet at a proper height above the floor with the hinge mounting on the right.

Installing the Cabinet

The FACP can be flush-mounted or wall-mounted. The dimensions for wall-mounting are shown in Fig. 2-1.

 Mark and predrill holes in the wall for the three keyhole mounting bolts using the dimensions illustrated in Fig. 2-1.

 Install three fasteners in the wall with the screw heads protruding.

 Using upper 'keyhole' place back box over the three screws, level and secure.

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

- Dimensions for flush-mounting are shown in Fig. 2-2.

- Hole distance for flush-mounting: 640mm x 380mm x 113.5mm

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Power

- WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized

AC Power and Earth Ground Connection

Primary power required for the FACP is 120VAC, 60 Hz, 2.4A or 220VAC, 50 Hz, 1.2A for the FACP. Over-current protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14AWG (2.00mm with 600 volt insulation rating. Make certain that the AC mains circuit breaker is off before wiring any connections between the mains and the control panel. Connect power supply to the Terminal XT1, as shown in Fig. 2-3. Note: Verify all cables are correctly connected before connecting power supply

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Connect a wire from the grounding stud in the cabinet to a known solid earth ground in the building. Refer to Fig. 2-1 for location of the stud. This connection is vital for maintaining the control panel's immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked

Battery Power

- Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries

- WARNING: Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention

24VDC Power Output Connection

- 24VDC power output is Power-limited,supervised and regulated

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Relays (For Common Use)

- The FACP provides three relays, with contacts rated 2.0A @ 30VDC (resistive).

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Relay contacts shown with power applied to panel and no active fault, alarm or supervisory.

Notification Appliance Circuits (NAC)

- There are two Style Y (Class B) NAC outputs on the loop interface board. Each circuit is capable of 1.2A of current. Total current in alarm for all external devices cannot exceed 2.4A. Use System Sensor's UL listed sounders (see Section 1.6.5) that can work at regulated 24VDC. Circuits are regulated, supervised and power-limited.

- Style Y (Class B) Notification Appliance Circuits, regulated , supervised and power-limited - 4.7 kOhm EOL

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Signaling Line Circuits (SLC)

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Connection of SLC:

C-9503 / C-M9503 / GST-LD-8322 Loop Isolator must be connected in SLC loop, each administrating a maximum of 30 addressable devices. The SLC can have at most 240 devices. Compatible devices are I-9102(UL) / JTY-GD-G3 Intelligent Photoelectric Smoke Detector, I-9103(UL) / JTW-ZCD-G3N Intelligent Rate of Rise and Fixed Temperature Heat Detector, I-M9300 / GST-LD-8300 Addressable Input Module, and I-M9301 / GST-LD-8301 Addressable Output Module

UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25'' (6.35mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the GST-M200 is shown below

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Programming

Programming Data Entry

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

 Press MODE to enter operation menu;

 Under operation menu, pressing number keys can lead the FACP to sub-menus or corresponding functional status. Pressing ESC or ENTER can exit the present level.

  In input mode, the cursor indicates the position. number keys directly. If ''*'' is to be used, press the ''*'' key. If more than one data section exists, the cursor goes to the next section after the present section is finished. Press TAB to go to the next, or △ = , = ▽ to the previous. Within a section, press △

Description of Programming Screens

If MODE is pressed, six options will be available on the screen as shown in Fig. 3-1: Read Status, Programming, Autoprogram, Disable/Enable, Walk Test, and Configure Item. In which Read Status and Programming have multiple levels of submenu that can be accessed by pressing number keys, or exited at any time by pressing ESC repeatedly.

GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

Programming and Passwords

There are two user-programming levels:

 Master password is used for programming panel specific data relating to device types, messages, control panel functions, etc.

 Maintenance password is used by a qualified operator to access features such as Autoprogram, Disable/Enable, Walk test and Configure Item.

 

 

 

Have 0 comment, evaluate about GST200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual

TVAdministratorsAdministrators

Welcome, honored guests. Please leave a comment, we will respond soon

Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.12072 sec| 3716.703 kb