Forede Sprinkler Heads 74 and 100 Degrees C

Manufacture: forede
Product code: Frede Fire Sprinklers For Storage

Frede Fire Sprinklers For Storage is installed in places where the slope of the roof or ceiling does not exceed 170mm / m
❌  Sprinklers must be installed parallel to the ceiling or ceiling  Nozzle spacing Spraying must not be less than 2.4m and not larger than 3.7m When the height of the protected object is greater than 7.5m or the clearance height of the protected space is greater than 9m, the nozzle distance spray should not be more than 3m

Zalo

Consulting hotline: 0944934114
Product information

Induction of fire sprinkler for storage

Frede Fire Sprinklers For Storage is a key component of an automatic sprinkler system that has special advantages for the protection of tall warehouses, can be used in paper product warehouses and protects high tire warehouses. su. The fusible connector is connected by two equal length connectors through a thin layer of solder, when the operating temperature is reached, the solder layer melts, the connecting parts are separated and the nozzle The water began to spew fire.

Specifications

K K17 @ US (242 @ Metric)
Size

DN20 (3/4 ")

Connections type BSP (NPT Tùy chọn)
Structure Brass
Element Alloy
Light bulb NBR (Teflon Optiona)
Coating

Natural brass

Working temperature 74 ° C, 100 ° C

Featured

1) Use molten alloy because sensitive components have stable performance, accurate operating temperature and fast response speed.

2) By installing ESFR sprinklers in the overhead system, layering sprinklers on each shelf can be eliminated, thus simplifying the system and saving investment costs.

Application Mainly used to protect most common materials covered or unfilmed, including non-foamed plastics packed in cartons.

- The maximum stack height is 10.5m.

- Can be used in the stock of cylindrical and rubber packaging paper products. Tire storage.

 

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about Forede Sprinkler Heads 74 and 100 Degrees C

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
Online support
0.13872 sec| 4318.797 kb