Forede K363 fire sprinkler for storage
Forede K363 fire sprinkler is installed in places where the slope of the roof or ceiling of the building does not exceed 170mm / m The sprinkler plate must be installed parallel to the ceiling or ceiling ,The nozzle distance should not be less than 2.4m and not greater than 3.7m ,When the height of the protected object is greater than 7.5m or the clearance height of the protected space is greater than 9m, then nozzle distance should not be more than 3m
Induction of fire sprinkler K363 for storage
The forede K363 fire sprinkler for storage is a sprinkler head that uses molten alloy welded parts as the temperature sensing element.
K | K25 @ US (363 @ Metric) |
Size | DN25 (1 ") |
Connections | BSP (NPT Optional) |
Structure | Brass |
Glass ball | molten alloy |
Surface | Natural brass |
Temperature | 74 ° C, 100 ° C |
1) Use molten alloy because sensitive components have stable performance, accurate operating temperature and fast response speed.
2) By installing ESFR sprinklers in the overhead system, layering sprinklers on each shelf can be eliminated, thus simplifying the system and saving investment costs. It is mainly used to protect most common materials covered or unfilmed, including non-foamed plastics packed in cartons.
The maximum stack height is 10.5m. It can also be used in cylindrical and rubber packaging paper products warehouses. Tire storage.