DESCRIBE
• Safety internal barrier, powered by zones and with Zener diodes for use in conventional fire detection systems to protect hazardous areas.
• Each zone contains two stages of pulse-tested Zener diodes or forward connections and an 'easy' termination resistor. At In the event of a power failure in a safe area, voltage limiting diodes can reach the hazardous area and current limiting resistors. Fuses protect the diodes and two voltage limiter stages ensure continued safety in the event of any stage failure. No circuit may use active output current limiter
• Note: Note that the unit ground connections are made via a DIN rail connection (this product MUST be grounded).
CHARACTERISTICS
• 1 channel
• DC version, positive polarity
• Color-coded mobile terminals
• Accommodates conductors up to 2.5mm²
• The input circuit is protected against reverse polarity
• DIN rail mounting
• ATEX II classification
SPECIFICATION
• Number of channels: 1
• Maximum series resistance 327Ω
• Maximum operating voltage 26.9V DC, 26.5V DC at 10 A
• Short circuit current up to 93 mA
• Fuse rating (continuous) 50 mA
• Storage temperature 25°C ~ +70°C
• Operating temperature 20°C ~ +60°C (continuous working)
• Relative humidity up to 95% non-condensing
• Dimensions: 110 x 115 x 12.5 mm
• Weight: 150 g