FM200 Automatic Fire Suppression System
Fm200 automatic fire suppression system in most buildings and ordinary places, water fire-fighting systems are generally used to extinguish fires, but in some special places such as data processing room, mobile communication base station, power distribution room, engine room, library and archives, precious cultural relics, exhibition hall warehouse Other places need to use gas fire extinguishing systems to extinguish fires to minimize fire losses and protect related equipment.
FM200 Automatic Fire Suppression System
Pipe network type heptafluoropropane fire extinguishing device consists of bottle rack, fire extinguisher bottle, container valve, high pressure hose, liquid check valve, header, safety valve, distributed pipe, selector valve, pressure signal device, fire extinguishing agent conveying pipe, Nozzle, starter bottle, drive, starting pipe, starting gas check valve, etc.
1.Piping Network Type
It is an intelligent automatic fire extinguishing system. According to the requirements of different application places, it can be composed of unit independent system and combined distribution system. It adopts full flooding fire extinguishing method to achieve fire protection for single protection zone and multiple protection zone. It has advanced technology, high fire extinguishing efficiency and convenient maintenance. The system has three startup modes: automatic, manual and mechanical emergency operatio
2.Cabinet Type
The cabinet fire extinguishing device is also called a pipeless network fire extinguishing system and a prefabricated fire extinguishing system, and is composed of a fire extinguishing agent storage bottle, a container valve, a drive, a high pressure hose, a pressure signal device, a nozzle, a cabinet body, and the like.
There is no need to install a fire extinguishing agent transfer pipe, and there is no need to set up a dedicated storage room. The device is placed in the protection zone, and when a fire occurs, the fire extinguishing agent is sprayed directly the protection zone.
The fire extinguishing agent has no pipeline loss, and the fire extinguishing speed is faster and more efficient.
The device has two automatic and manual activation modes.
Product Specification of clean agent system fm200
SYSTEM DATA |
|||
Model | QMQ4.2/90N-FRD | QMQ4.2/120N-FRD | QMQ4.2/150N-FRD |
Cylinder Capacity |
90L | 120L | 150L |
Cabinet Size(cm) | 90×50× 145 | 90×50× 160 | 90×50× 190 |
Max. W. P |
5.3Mpa |
||
Storage Pressure |
4.2Mpa |
||
Working Temperature |
0~50°C (System room) | ||
Operating Voltage |
AC 220 V |
||
Back-Up Power |
DC 24 V |
||
Discharging Time |
≤10 S |
||
System Startup Method |
Automatic / Manual / Emergency operationOperation |
Features:
-Fast fire extinguishing speed, high efficiency and strong initiative
-Clean
-Safety
-Environment protection
-Cost-effective
Applications
1.Computer Rooms
2.Data Processing Centers
3.Telecommunications And Communication Facilities
4.Process Control Centers
5.Expensive Medical Facilities
6.Valuable Industrial Equipment
7.Museums
8.Art Galleries
9.Libraries