Electrically Actuated Manual Reset Deluge Valve DE RCL

Product code: DE RCL

Electrically controlled deluge/pre-action valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when a 3w solenoid valve is energized. The valve must be manually reset following automatic actuation using the RCL relay’s knob. An emergency manual release valve is fitted as standard.

Zalo

Consulting hotline: 0944934114
Product information

FEATURES & BENEFITS

High pressure (PN25/375psi), high flow deluge systems

Automatic or local manual emergency actuation

Hazardous, flammable & explosion classified area fire suppression

Superior design featuring exceptionally low pressure losses at high flow rates

Low lifelong maintenance costs due to straightforward design

Applicable for fresh or brackish water, seawater & foam

Out of box fully assembled & tested valves

Factory trimmed for vertical or horizontal installations without modification

Extensive valve & trim materials selection and corrosion protection coating

CERTIFICATION & COMPLIANCE

Electrically Actuated Manual Reset Deluge Valve DE RCL

• ANSI FCI 70-2 Class VI seat leakage class

• UL listed under VLFT category

• Fire tested to EN ISO 6182-5:2006 (2”- 6” only)

• Lloyd’s & ABS approvals

TYPICAL APPLICATIONS

Automatic or Manual Actuated Fire Suppression Systems

Petrochemical, Oil & Gas Installations

Tunnels

Power Generation, Transformer & Transmission Plants

Flammable Storage

Hangars & Airport Terminals

Onshore / Offshore

Mining

OPERATION

The basic control valve [1] used in this deluge system is a direct-sealing elastomeric diaphragm, hydraulically operated control valve engineered specifically for fire protection systems. The system includes a 3/2-way N.O. solenoid [10] as the interface between the fire alarm control panel - monitoring heat, smoke or flames - and the deluge valve.

In the standby position, the deluge valve is held closed by the upstream water pressure, trapped in the valve’s control chamber. The water pressure enters the control chamber through the priming line ball valve [2], a Y-type strainer [3], a check valve [4] and a T-restrictor [5].

Under fire conditions, a fire alarm control panel (F&G panel) energizes the 3/2-way N.O. solenoid (or de-energizes the coil of a continuously energized ED 100% normally closed solenoid for SIL 3-4 rated systems). The pressure in the RCL 28-2UL relay valve (manual-reset latching relay) [9] drops, latching it open and allowing the water to drain the deluge valve’s control chamber. The deluge valve opens instantly and allows water to flow the pipeline and through the open sprinklers over the
protected area.

Manual emergency actuation is enabled by opening the emergency manual activation valve [6]. The deluge valve opens instantly and allows water to flow the pipeline and through the open sprinklers over the protected area.

To reset the deluge valve and close it, the RCL 28-2UL relay’s knob must be rotated to unlatch it, thus re-admitting water the valve’s control chamber

Electrically Actuated Manual Reset Deluge Valve DE RCL

TYPICAL MATERIALS

Electrically Actuated Manual Reset Deluge Valve DE RCL

(1) Petrochemical, Oil & Gas

(2) Refer to materials selection guidelines, Engineering Data - Materials: Ductile Iron A-536 65-45-12; Cast Steel A-216 WCB; Cast Steel A-352 LCB; Austenitic
Stainless Steel A-351/CF8M; Super Duplex 2507; Nickel-Aluminum-Bronze B-148 UNS C95800

(3) Consult factory

Electrically Actuated Manual Reset Deluge Valve DE RCL

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comment, evaluate about Electrically Actuated Manual Reset Deluge Valve DE RCL

Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Comment
Click here to rate
Sender information
Product portfolio
0.14674 sec| 4332.789 kb