Apollo 55000-720APO Isolator
The isolator is spaced on the loop and ensures that
⭐in case of short circuit, only the part between the isolators will be affected.When the short circuit is removed, the isolator will automatically restore power and data for the isolated part.
Specifications
Longevity | 10 years |
Protocol Voltage (Min.) Protocol Voltage (Max.) Protocol Voltage Maximum Power On Time Reconnect Voltage (Min.) Reconnect Voltage (Max.) Reconnect Voltage (VSCmin – VSCmax) Quiet Stream Static Current Tested On Resistance Impedance |
Protocol Voltage (Min.)5V 9V 5 to 9V peak to peak <1 second 12,9V dc 18V dc 12,9 to 18V dc 35μA 24V dc 200000000Ω |
Humidity (Min.) Humidity (Max.) Notes About Humidity Humidity Operating Temperature (Min.) Operating Temperature (Max.) O perating Temperature Storage Temperature (Min.) Storage Temperature (Max.) Storage temperatures |
0% RH 95% RH no condensation or freezing 0% to 95% (no condensation or freezing) -20 ° C 60 ° C -20 to 60 ° C -30 ° C 80 ° C -30 to 80 ° C |
Approve |
CPD DNV.GL LPCB VdS |
Weight Color Material Material Terminal Product Depth Product Diameter |
100g White Polycarbonate Nickel plated stainless steel 24mm 100mm |
You can refer to products genuine fire alarm equipment...HERE
Have 0 comment, evaluate about Apollo 55000-720APO Isolator
TVAdministratorsAdministrators