VSH1230, Viking Clean Gas Fire Extinguishing System UL FM Standard
Viking Clean Gas Fire Extinguishing System UL/FM VSH1230 is an effective fire fighting system for kitchens, bedrooms, banks... 3M
™ Novec 1230
™ liquid system ensures no equipment damage ,Contact for technical advice: 0917.911.114
VSH1230, UL/FM Standard Viking Clean Air Fire Extinguishing System uses 3M™ Novec 1230™ flame retardant liquid that will not damage electronics and leave no residue. The high safety margin makes it extremely safe for people working in protected areas. With an ozone depletion potential of 0.0, an atmospheric lifetime of only five days, and a global warming potential of 1.0, the VSH1230 system is a long-term replacement for Halon.
High pressure means smaller tank and less floor space. The 725 psi system allows for longer pipeline runs, smaller pipe sizes, remote tank location, and multi-zone protection a single trigger. VSH1230, the only Viking UL/FM Novec™ 1230 Clean Gas Fire Extinguishing System approved for use with selector valves, Viking offers the cost savings and system flexibility to protect large areas.
Equipment for VSH1230, Viking Clean Gas Fire Extinguishing System UL/FM
- Accessories for fire fighting system when clean
1. Releasing Devices (Bộ kích hoạt)
UL/FM . standard
• Maximum operating temperature: UL / ULC 0ºF to 81.5ºF (-18ºC to 27.5ºC), FM 0ºF to 122ºF (-18ºC to 50ºC) Discharge device
• Nominal voltage: 24 V / DC +/- 15%
• Rated current: 0.5 A +/- 10%
• Maximum Monitoring Current: 20 mA
• Punctuality: 100%
2. Clean gas fire extinguisher
The Viking VSH1230 fire suppression system uses 3M™ Novec™ 1230 extinguishing fluid which is stored in the system's extinguishant tank(s) until the system is activated.
Standard :
- UL ListedE: Clean Agent Extinguishing System Unit - FM ApprovedE: Clean Agent Fire Extinguishing System
Specifications
• Working pressure: 360 psi (25 bar) or 725 psi (50 bar) at 70°F (21°C)
• Max. Working pressure: 508 psi (35 bar) or 870 psi (60 bar) at 122°F (50°C)
• Pressure response at Bursting Disc for 360 psi (25 bar) System: 900 psi (62 bar) at 68°F (20°C)
• Bursting Disc return pressure for 725 psi (50 bar) System: 1276 psi (88 bar) for 2 valves, 1291 psi (89 bar) for 1-1/2 valves at 68°F ( 20°C)
Specifications of pressure gauge
• FK-5-1-12 (NovecTM 1230)
• 360 psi (25 bar) system:
• Maximum pressure: 725 psi (50 bar)
• Indication range: 0 to 508 psi (35 bar)
• 725 psi (50 bar) system:
• Maximum pressure: 1160 psi (80 bar)
• Indicator range: 0 to 870 psi (60 bar)
• Nominal size: 2 meters (50 mm) •
Precision class: 1.6
3. System fire extinguishing agent VSH1230
The Viking VSH1230 fire suppression system uses 3MTM NovecTM 1230 fluid, which is a next generation alternative to Halon. VSH1230 is used to protect the contents of areas containing valuable equipment or documents, including, but not limited to Museums, Banks, Cleanrooms, Data Centers, and Libraries. NovecTM 1230 leaves no residue behind, does not suffer ozone depletion and has the lowest atmospheric life for halocarbon substitutes. NovecTM 1230 extinguishes fires by absorbing heat. The VSH1230 results in less time, less cleanup, less business disruption and eco-friendly.
Standard
- UL Listed: For the Clean Agent Fire Extinguishing System
- FM Approved: For theClean Agent Fire Extinguishing System
Specifications Minimum and maximum liquid storage temperature: 0°F to 122°F (-18°C to 50°C)
- Minimum and maximum temperatures of protected spaces per UL and FM: 60°F to 80°F (15.6°C to 26.7°C)
- Chemical formula: CF3CF2C (O) CF (CF3) 2
- Chemical name: Dodecafluro-2-methyl-pentane-3-one
- Molecular Weight: 316.04ISO Indication: FK-5-1-12Spec
- Weight 68°F (20°C): Density 3.04 lbs/gal (1.41 kg/l), Saturated Liquid @ 77°F/4.69 psi (@25°C / 1,013 bar ): Density 99.9 kbm/ft2 (1.60 g/ml), Gas 1 ATM @ 77°F / 4.69 psi (@25°C / 1,013 bar): 0.852 lbm/ft3 (0.0136 g) /ml)
- Freezing point: -162.4°F (-108°C) Boiling point: 120.5°F at 14.69 psi (49.2°C at 1,013 bar)
- Density, 1 ATM @ 77°F / 4.69 psi (@ 25°C / 1,013 bar): 1.17 ft3/lb (0.0733 m3/kg)
- Liquid viscosity @ 77°F / 4.69 psi (@ 25°C / 1,013 bar): 0.56 (0.41 centistokes)
- Heat of vaporization @ BP: 37.9 BTU/lb (88.1 kJ/kg)
- Solubility of H2O in NovecTM 1230 @ 77°F / 4.69 psi (@ 25°C / 1,013 bar): <0.001% by wt.
- Vapor pressure @ 77°F / 4.69 psi (@ 25°C / 1,013 bar): 5.87 psig (0.40 bar)
- Dielectric strength (relative to N2 at 1 ATM): 2.3
4.VSH1230 System Clean Air Nozzle
In the VSH1230 Fire Extinguisher System, the discharge nozzle is used to apply the extinguishing agent during a calculated flooding period and uniformly distributed in the protected housing. Two types of nozzles are available for the VSH1230 Fire Extinguishing System:
180° nozzle sprays extinguishant in a semicircle around the nozzle
The 360° nozzle sprays the extinguishing agent in a full circle around the nozzle
Standard - UL Listed: Clean Agent Extinguishing System Unit - FM Approved: Clean Agent Fire Extinguishing System Specifications
• Minimum and maximum agent storage temperature: 0°F to 122°F
• (-18°C to 50°C)
• Minimum and maximum temperatures of protected spaces per UL and FM: 60°F to 80°F (15.6°C to 26.7°C)
• Minimum operating pressure: 111 psi (7.65 bar)
• Maximum operating pressure: 870 psi (60 bar)
• 180° radioactive discharge hose: 35'-9 9 (10.91 m)
• Drain hose 360° radius: 22'-7 (6.9 m)
• Maximum effective nozzle height: 14' (4.27 m)
• Extended maximum effective nozzle height: 17.9' (5.45 m) - with taller design being a prerequisite
• Maximum quantity of extinguishant per nozzle: 466 lbs (725 psi) 386.7 lbs (360 psi)
• Nozzle diameter of the nozzle: Orifice's diameter increment is 0.001 inch increments
• Thread sizes: 1/2, 1, 1, 1-1/2, and 2 NPT