HFP AP-2ASS, 16-zone c/w loop fire alarm cabinet Hochiki
HFP AS is a range of flexible open protocol fire alarm control panels compatible with existing HFP fire panel technology Available with one or two detection loops capable of hosting up to 127 devices The HFP AS uses leading-edge microprocessor-based electronics to provide a flexible control system with high reliability and integrity. Suitable for all small to medium sized fire detection systems, the HFP AS panel can be expanded and connected to become part of much larger systems if the need arises, thus providing provide future proof solutions for any installation. With its large graphic display and ergonomic buttons and control panel, the HFP AS control panel is simple and straightforward for installers, operator engineers and end users.
16 area LED indicators
2 programmable audio circuits
5 programmable inputs
3 programmable relays
Power supply 3A
Large graphic display
Real-time clock
11.26kg
Expandable 1 to 2 loops
EN54-2 / EN54-4 . Certified
Up to 512 additional programmable I/Os via HFP . I/O modules
Powerful, wide network cause and effect
Sensitivity adjustment and drift compensation
Can be connected to HFP . control board
Compatible with Focus and View repeaters
HFP scope-like interface
Store the last 500 events in the event log
Dial-up modem connection available
Compact, stylish enclosure
Installer friendly, removable equipment chassis
Different language variations and character sets available
Fully improved Preload Printer option to EN54-2 and EN54-4 . standards Parameter
Construction of 1.2mm . mild steel plate
IP rating IP30
Epoxy paint finish Color - BS 00 A 05 lid & box gray - fine texture Color - RAL 7047 panel & labels light gray - satin
Weight 6kg (standard board)
Display 8 lines of 40 characters graphic LCD
Mains voltage 110 or 230V AC 50 or 60 Hz. (Specify when ordering, default is 230V)
Main supply fuse 1.6A 250V
DC power supply rated 24V 3 Amps
Provides 24V . AUX
Consolidation at 500 milliamps
Maximum battery size 9Ah 12V (2 per board) (non-networked)
Fault contact rating 30V DC1 Amp X
fire contact rating 30V DC1 Amp
30V DC1 Amp . alarm contact rating
Sounder output rating
Consolidation at 1 Amp
400 milliamp detection loop
Dimensions (mm) 385 x 310 x 90