CO2 automatic fire extinguishing system 5.7MPa 0.6kg L
Brand:xingjin ✔️Certification:CAL, CMA, CNAS, ILAC-MRA, CCC ,Model number:QME70 , Equipment nitrogen pressure :6.0 ± 1.0Mpa (20
℃) ,Spray time: ≤ 60s,Extinguish model:Inundated with , Working pressure:5.7MPa , Capacity :70L , Weight:42kg , Type:Pipe network ,Start mode:Auto, Manual Electrical, Mechanical Emergency Manual
Description:
Fire extinguishing systems are designed to extinguish fires in sensitive environments where water a fire hydrant is not a desired extinguishing agent. Popular areas where you'll find fire suppression systems include server rooms, machine rooms, combustible storage areas, museums, and data centers.
There are several different types of agents used in suppression systems to extinguish fires. In server rooms and environments where you have regional staff, you'll often find clean agent or inert gas degassing systems. In environments with few or no personnel, you will often find CO2 fire suppression systems. Areas where you'll find CO2 fire suppression systems include engine rooms, generator rooms, power stations, flammable liquid storage rooms, and around large industrial machines.
While CO2 fire suppression systems are highly effective in extinguishing fires, CO2 agents are also hazardous to health when compared to other agents. For this reason, you will see CO2 fire suppression systems most often in uninhabited environments.
Specifications
STT | Descriptions | Specifications |
1 | Model | QME70 |
2 | Capacity | 70Ltr |
3 | Gas weight | 42kg |
4 | Pressure | 5,7MPa |
5 | Max pressure | 12.4MPa |
6 | Spray time | ≤60 second |
7 | Maximum fill rate | 0,6kg / L |
8 | Size source | DC24V / 1.6A |
9 | Working pressure of release device | Van chứa: 19 ± 0,95MPa; Manifold: 15 ± 0,75MPa |
10 | Nitrogen pressure | 6,0 ± 1,0Mpa (20 ℃) |
11 | Environment temperature | 0 ~ 50 ℃ |
The components
The pipeline network type of CO 2 automatic fire extinguishing system is mainly composed of three parts. Fire fighting equipment and pipe fittings and electrical fittings.
Fire-fighting devices are such things, like cylinders for CO2 intake and storage, frames and actuators (nitrogen cylinders) to activate storage cylinders for waste discharge, etc.
Piping fittings are conduits for connecting fire fighting equipment and guides the protected area, such as high pressure galvanized steel pipes and flanges and elbows, etc.
Electrical accessories are those used to detect and monitor the entire protected area and control the entire system, as well as warn people to evacuate and prevent the fire spreading.
These three integrated units will be effective for automatic fire detection and monitoring, warning and extinguishing.
Operation Diagram