AIR-Intelligence HSSD continuously adapt their sensitivity to the environment in which they are installed, providing alarm thresholds which are 'relative' to the background particle levels in the protected area, instead of placing the alarm threshold at a fixed level relative to ambient conditions. At any time, the detector's performance remains constant, regardless of fluctuations in the normal background particle level. AIR-Intelligence detectors only respond to particle levels significantly above the expected background level, such as a genuine fire situation.
Features
High-sensitivity provided by laser-based forward light scatter mass detection and particle evaluation for reliable early warning detection
Four programmable alarm thresholds (Aux, Pre-Alarm, Fire 1 and Fire 2)
ClassiFire™ Perceptive Artificial Intelligence system
Dual Technology LDD 3D3 Laser Dust Discrimination and Elimination system
Technical Specifications
Particle Sensitivity Range: 0.003 to 10 micron
The Industry's Widest Sensitivity Range: 0.00046 to 7.62% obs/ft
RS-485 built-in as standard for networking and remote communications. Up to 127 detectors per loop with 4,000 ft. between devices.
RS-232 built-in for direct PC interface without the expense of high level interface equipment
Powered by 24-Volt DC regulated supply, low current draw
Listing & Approvals
FM Approved
cULus Listed
Have 0 comment, evaluate about AIR-Intelligence Smoke Detection HSSD
TVAdministratorsAdministrators