AH-0014, Horing High Sensitivity Smoke Detector
Wide-angle sensitivity smoke detector can reliably and quickly detect weak ultraviolet rays emitted by flames
⭐It will not react to room light, infrared or other light sources unrelated to real fire, Product code: AH-0014, Origin: Horing Taiwan, Contact 0917.911.114
Applications
- Plans with higher ceilings: theatres, gyms, storage, showrooms or warehouses, etc.
- Fire prone places: storage places with flammable goods, gas stations, factory workplaces, engine rooms, etc.
- Ventilated places: open markets, train stations, hotel lobbies, department stores, etc. (places where smoke and heat cannot be concentrated in the early stages of a fire)
- Other places: tunnels, computer rooms, etc. Installation Instructions
- Install in places where there are no obstructions.
- Avoid installation near mercury lamps, halogen lamps and disinfection lamps.
- Avoid installation in the sensitive range of welding sparks and radiation.
- CE certification
Model | AH-0014 | ||
Type | 2 wire | 3 wire | 4 wire |
Alarm | No | No | 0,8A @ 30V DC, 0,4A @ 125V AC |
Voltage range | 12 ~ 30V DC | ||
Current alarm @ 24V DC 470Ω | 40mA | 40mA | 35mA |
Standby current @ 24V DC 470Ω | dưới 100μA | ||
Sensor type | Ultraviolet ray | ||
Sensitivity angle | 120 ° | ||
Sensitivity | can detect 15mm flames at a distance of 3 m | ||
Temperature | -10 ℃ ~ +55 ℃ | ||
Material | Flame Retardant Plastic | ||
Size | 111mm (Dia.) X 47mm (H) | ||
Weight | About 170g | ||
Color | White |