Unipos VIT 01 wireless fire alarm cabinet
Supply wireless fire alarm cabinet, price list of wireless fire alarm equipment Unipos, Unipos vietnam wireless fire alarm equipment ata, independent wireless fire alarm smoke alarm system, best wireless fire alarm system, system ata wireless fire alarm, central fire alarm cabinet, firesmart wireless fire alarm, Unipos VIT 01 wireless fire alarm cabinet is designed to secure, manage and control fire alarm devices. The use of radio communication between the control panel and the fire detector makes it suitable for installation in premises where unwanted cables are located.
PRODUCT DESCRIPTION
- Unipos VIT 01 wireless fire alarm cabinet is designed to secure, manage and control fire alarm devices. The use of radio communication between the control panel and the fire detector makes it suitable for installation in premises where unwanted cables are located. The control panel is designed and manufactured according to the requirements of ЕN 54-2/4 and EN 54-25. Dashboard works in conjunction with:
- Automatic fire detectors VIT20, VIT30, VIT60.
- VIT50 manual call point.
- Router VIT02. Basic functional features:
- Set operating modes and parameters of fire detectors, communication and output controllers through the built-in keyboard.
- Control to detect fire the base, battery status.
- Control the radio signal level of the device.
- Option to change the parameters of the fire detector.
- LCD screen to display the operating modes of the system.
- LED lights for emergency and extreme situations in the area and throughout the system.
- Non-volatile storage memory, which stores up to 4096 events, indicates the time and type of events and allows perfect analysis of authorized personnel actions and possible problems in the process fire safety of the premise.
- User-friendly test mode for all system components, providing full control over the health of the protected premise.
- Test and 16 different channels to establish a radio connection.
- Automatic recovery in fault condition, after the reason, causing the error has been removed.
- Built-in RS232/RS485 serial interface for connection with personal computer or other external devices.
- Compatible with different installation designs, within control panel resources.
Specifications Maximum number of devices/zones: 32/15 Wireless network parameters
- Frequency: 2.4 GHz
- Maximum number of devices in the network: 32
- Maximum number of routers in the network: 6
- Maximum number of devices directly connected to the Control Panel: 20
- Maximum number of fires of detectors connected to the router: 14
- Maximum number of message retransmissions via router: 5 Controllable output: 2 pcs
- Type: potential, relay
- Electrical features: (24 ± 5) V DC / 1 A Relay output for fire condition: 1 pc
- Type: no potential, switched
- Electrical features: 3A / 125V AC; 3-way voltage / 30V Relay output for fault condition: 1 pc
- Type: no potential, switched
- Electrical features: 3A / 125V AC; 3-way voltage / 30V Sign of registered events: LED
- Light indicator: liquid crystal display
- Text messages: 4 lines, 20 characters per line, cyrillic, back-lit
- Sound: built-in audio Power supply Main Supply
- Voltage: 220 / 230V
- Frequency: 50 Hz Backup power supply (battery)
- Battery type: lead, gel electrolyte
- Number of batteries: 2 pieces
- Connection: serial connection
- Nominal voltage of connected backup battery: 24V DC
- Nominal capacity 20: (1,2-4, 5) Ah
- Terminal discharge voltage: 17.6V
- Charging voltage: 28V
- Consumption when supplying backup battery: <180mA at 24V Overall dimensions: 313х218х85 mm Weight (excluding backup battery) not more than: 1,440 kg