Tyco Ty3236 Pendent Sprinkler Head

Product code : ty3236

+++ Tyco Ty3236 Downward Sprinkler Head +++ Pressure 175 psi (12.1 bar). +++ Quick Response Type +++ Special nozzles Distributing types of fire sprinklers Ty315, TY325....

Consulting hotline: 0944934114
Product information

Tyco Ty3236 Downward Sprinkler Sprinkler-Flat Nozzle belongs to the special TY-FRFS series of quick-response sprinklers.

Tyco Ty3236 . Downward Sprinkler Head

- Product line: TY-FRFS

- Injection coefficient: K=80 LPM/bar½

- Size of glass tube: 3mm

Description of Tyco Ty3236 . Pendent Sprinkler Head

- Has a flat design compared to standard sprinklers, allowing them to be used with lower clearances above open ceilings and shelves in accordance with CEA 4001 “Sprinkler Systems Planning and Installation” or EN12845 “Automatic Sprinkler Systems

– Design, Installation and Maintenance”.

- Can be equipped with a protective frame to avoid physical collisions.

- Plating material: copper

- Activated by glass tube

Tyco Ty3236 . Pendent Sprinkler Head

Tyco Ty3236 . Pendent Sprinkler Head Specifications

- Meet standards: VdS; CEA 4001; EN12845; LBCP

- Maximum working pressure: 175 psi (12.1 bar).

- Injection coefficient: K= 80 LPM/bar½

- Nozzle size: 1/2 inch NPT (DN15).

- Activation temperature:

+ 135°F (57°C) Orange glass tube.

+ 155°F (68°C) Red glass tube.

+ 175°F (79°C) Yellow glass tube.

+ 200°F (93°C) Green glass tube.

+ 286°F (141°C) Blue glass tube.

Xem thêm
Rút gọn
Frequently asked questions

You will receive a quote from us as soon as possible..

Have 0 comments, reviews about Tyco Ty3236 Pendent Sprinkler Head
Welcome, honored guests. Please leave a comment, we will respond soon
Reply.
Sender information
Bình luận sản phẩm
Write a comment
Product portfolio
0.41665 sec| 3997.438 kb