Tyco Sprinkler TY7229
Model ESFR-17, TY7229, K=16.8,Pendent Sprinkler is a genuine sprinkler combined with a 5kg CO2 fire extinguisher 15 channel Horing fire alarm cabinet How to CM-WT32L Smoke Detector 8 channels Horing fire alarm Fire alarm Horing QA16
K 16.8
SlopeMaximum 2 in.12 in (16,7%)
Maximum coverage area100 ft2 (9.3 m2)
In some cases, installed stan-dards allow for larger coverage areas.
Minimum coverage area 64 ft2 (5.8 m2) per NFPA 13/FM 2-0Maximum Spaces12 ft (3.7 m) for building heights up to 30 ft (9.1 m) 10 ft (3, 1 m) for building heights greater than 30 ft (9.1 m)
Minimum clearance 8 ft (2.4 m) Minimum cargo clearance 36 in. (914 mm) Ceiling-to-ceiling distanceNFPA - 6 in. to 14 in. (152 mm to 356 mm) Centerline of the thermal sensing element ceiling to ceiling
FM 2-0 for Storage Sprinklers.